Model 3095FB Multivariable Transmitter with Modbus Protocol
Modbus Protocol Guide
Page 51 of 79
0058
0119
(cont)
0407
(cont)
7
AD
DP signal below Lower Range Limit - 10%
0059
6
AD
SP signal above Upper Range Limit + 10%
0060
5
W
SP signal above Upper Range Limit
0061
4
SP signal above Upper Operating Limit
0062
3
SP signal below Lower Operating Limit
0063
2
W
SP signal below Lower Range Limit
0064
1
AD
SP signal below Lower Range Limit - 10%
0065
0
AD
SP sensor shorted
0066
0120
0408
15
AD
SP signal is unreasonable - open bridge
0067
14
AD
PT signal above Upper Range Limit + 10%
0068
13
W
PT signal above Upper Range Limit
0069
12
PT signal above Upper Operating Limit
0070
11
PT signal below Lower Operating Limit
0071
10
W
PT signal below Lower Range Limit
0072
9
AD
PT signal below Lower Range Limit - 10%
0073
8
AD
RTD is disconnected
0074
7
AD
ST signal is above Upper Internal Limit
0075
6
AD
ST signal is below Lower Internal Limit
Not A
v
ailable as Discrete
Inputs
5
Reserved
4
Reserved
3
Reserved
2
Reserved
1
Reserved
0
Reserved
0121
0409
15
AD
Sensor module is NOT updating
Table 8-1 Mapping of Status Bits to Coils, Input Registers, and Floating Point Registers
Discrete
Input
Address
Input
Register
Address
Floating
Point
Register
Address
Bit
Position
Attributes
Description