Table 5-2 identifies corrective actions for 3095FB alarms and events.
TABLE 5-2. Rosemount 3095FB Alarm and Event Summary
Floating
Point Reg./
Bit Posit.
Sets
Alarm/
Warning
Flag?
Alarm
Description
Action
20407
15
Calibration flag
Indicates that the host has set the calibration flag. No action required.
For more information, see page 31 in the Modbus Master Document.
20407
14
Critical alarm: PVs may not
be valid
Summation alarm flag.
This register is set if any Alarm (A) register is set.
20407
13
Warning: PVs outside
specifications
Summation warning flag.
This register is set if any Warning (W) register is set.
20407
12
A
DP signal exceeded Upper
Range Limit + 10%
This display means that the transmitter differential pressure reading
exceeds its sensor limits by more than 10%. There are two possible
causes. Either the transmitter is overpressured, or it has a sensor
malfunction. Check the pressure input to the transmitter. If an
overpressure condition exists, correct it. If not, replace the sensor
module as described on page 5-7.
20407
11
W
DP signal exceeded Upper
Range Limit
No action required.
20407
10
DP signal exceeded Upper
Operating Limit
No action required.
20407
9
DP signal is less than Lower
Operating Limit
No action required.
20407
8
W
DP signal is less than Lower
Range Limit
No action required.
20407
7
A
DP signal is less than Lower
Range Limit - 10%
This display means that the transmitter differential pressure reading
exceeds its sensor limits by more than 10%. There are two possible
causes. Either the transmitter is underpressured, or it has a sensor
malfunction. Check the pressure input to the transmitter. If an
overpressure condition exists, correct it. If not, replace the sensor
module as described on page 5-7.
20407
6
A
SP signal exceeded Upper
Range Limit + 10%
This display means that the transmitter absolute (or gage) pressure
reading exceeds its sensor limits by more than 10%. There are two
possible causes. Either the transmitter is overpressured, or it has a
sensor malfunction. Check the pressure input to the transmitter. If an
overpressure condition exists, correct it. If not, replace the sensor
module as described on page 5-7.
20407
5
W
SP signal exceeded Upper
Range Limit
No action required.
20407
4
SP signal exceeded Upper
Operating Limit
No action required.
20407
3
SP signal is less than Lower
Operating Limit
No action required.
20407
2
W
SP signal is less than Lower
Range Limit
No action required.
20407
1
A
SP signal is less than Lower
Range Limit - 10%
This display means that the transmitter absolute (or gage) pressure
reading exceeds its sensor limits by more than 10%. There are two
possible causes. Either the transmitter is underpressured, or it has a
sensor malfunction. Check the pressure input to the transmitter. If an
overpressure condition exists, correct it. If not, replace the sensor
module as described on page 5-7.