Model 3095FB Multivariable Transmitter with Modbus Protocol
Modbus Protocol Guide
Page 19 of 79
2.6.2 Reading and Writing 16 Bit Registers
2.6.3 Reading and Writing Bit Registers
If the returned input quantity is not a multiple of eight bits, the remaining bits in the final
data byte will be padded with zeros (toward the high end of the byte). In this case all four of
the bits that were asked for were ON (0000 1111). The rest of the byte was padded with
zeros.
Function 04: Reading 16 Bit Register Data
Address
Function
Starting reg-
ister
# of registers
Error check
Query
01
04
00 12
00 01
XXXX
Address
Function
Byte count
Register data
bytes
Error check
Response
01
04
02
00 86
XXXX
Function 16: Writing 16 Bit Register Data
Address
Function
Starting
register
# of reg-
isters
byte
count
Register
data bytes
Error
check
Query
01
10
00 30
00 01
02
00 24
XXXX
Address
Function
Starting
register
# of reg-
isters
Error
check
Response
01
10
00 30
00 01
XXXX
Function 02: Reading Bit Registers
Address
Function
Starting reg-
ister
# of registers
Error check
Query
01
02
00 3A
00 04
XXXX
Address
Function
Byte count
Register data
bytes
Error check
Response
01
02
01
0F
XXXX