Model 3095FB Multivariable Transmitter with Modbus Protocol
Modbus Protocol Guide
Page 39 of 79
Maximum Integer:
The maximum integer is the upper limit for the scaled integer output.
If the measured value derives an integer higher than the maximum integer or lower than 0,
the maximum integer plus one will be returned. Also, if any of the error conditions
described in Section 5.3.2 occur the affected scaled integers will be set to the maximum
integer plus one. The maximum integer can be any value from 0 to 65534. The default
maximum integer is 65534.
Table 5-9 PV Scaled Integer Maximum Integer
Modbus Access
DESCRIPTION
Address
Address
Type
Attributes
Functional
Area
Data / Control
125
Holding
register
RW
PV Scaled
Integers
Maximum Integer (applies to all
PVs)
*Attributes: R/W = Read/Write, RO = Read Only, WP = Write Protected
**These registers are available at multiple Modbus addresses (see Section 2.3 located in
the
Modbus Protocol Guide
)