Reference Manual
00809-0100-4738, Rev DA
May 2006
4-17
Rosemount 3095FB
Figure 4-15. Sensor Selection and Trim Screen
2.
SP Offset (zero) and Slope (span) Trim
a. Select SP from the
Sensor Selection
heading, and click
Offset
and Slope Trim
.
b. Enter the
Offset Trim Point
and
Slope Trim Point
values that will
be applied by a reference device, and click
Trim
.
c. Apply the offset trim value.
• If using a vacuum pump, pull a vacuum to both the high and low
sides of the transmitter. Wait for the measured value to stabilize,
and click
OK
.
• If vented to atmosphere and using a barometer, wait for the
measured value to stabilize, and click
OK
.
d. Using a deadweight tester, apply the desired slope trim value (high
pressure value) to both the low and high sides of the transmitter.
Wait for the measured value to stabilize, and click
OK
.