![Rosemount 3095FB Скачать руководство пользователя страница 49](http://html.mh-extra.com/html/rosemount/3095fb/3095fb_reference-manual_1487388049.webp)
Model 3095FB Multivariable Transmitter with Modbus Protocol
Modbus Protocol Guide
Page 18 of 79
Function 16: Writing Floating Point Data in a 32-bit Register
Address
Function
Starting
register
# of reg-
isters
byte
count
Register
data bytes
Error
check
Query
01
10
1C F0
00 01
04
43 66 00 00
XXXX
Address
Function
Starting
register
# of reg-
isters
Error
check
Response
01
10
1C F0
00 01
XXXX
Function 70: Writing Floating Point Data using a 32-bit Function
Address
Function
Starting
register
# of reg-
ister
pairs
byte
count
Register
data bytes
Error
check
Query
01
46
01 A0
00 01
04
43 66 00 00
XXXX
Address
Function
Starting
register
# of reg-
isters
pairs
Error
check
Response
01
46
01 A0
00 01
XXXX