Model 3095FB Multivariable Transmitter with Modbus Protocol
Modbus Protocol Guide
Page 20 of 79
When forcing a coil there are only two valid values that can be sent to the coil. The value
$FF00 will force the coil to 1(ON) and $0000 will force the coil to 0(OFF).
Function 05: Forcing a Single Coil
Address
Function
Coil address
Force data
Error check
Query
01
05
00 02
FF 00
XXXX
Address
Function
Coil address
Force data
Error check
Response
01
05
00 02
FF 00
XXXX