Device functions
Version 1
UPT-6006
Page 51
Part 2 of 3: Error messages (warnings)
NOTE:
The specified error messages are first output as warnings (actual value output switches between two
values; alarm LED flashes; alarm relay is not active). After the START signal is activated, it is output as a mal-
function (actual value output no longer changes, see bold-italic values; alarm LED is permanently lit; alarm relay
is active).
Error no.
Actual
value
output
Voltage
[V]
Cause
Measure if initial start-
up
Measure if machine in
operation, heating ele-
ment not changed
8
104
5.33
10
Current signal incorrect
Impulse transformer incor-
rectly sized
Perform
AUTOCAL,
Check transformer speci-
fication,
Error ranges
Error ranges
(“Loose connection”)
105
Voltage signal incorrect
Impulse transformer incor-
rectly sized
106
Voltage and current signal
incorrect
Impulse transformer incor-
rectly sized
302
Temperature too low
Calibration not performed
Loose connection
Ambient temperature fluctu-
ates
Perform
AUTOCAL
and/or
Error ranges
(“Loose connection”)
303
Temperature too high
Calibration not performed
Loose connection
Ambient temperature fluctu-
ates
9
211
6.00
10
Data error
Perform
AUTOCAL
Perform
AUTOCAL