Commissioning and operation
Page 16
UPT-6006
Version 1
7.2.2
Configuration of the rotary coding switch for temperature range and alloy
The setting of the rotary coding switch for temperature range and alloy can be overwritten by the
parameter data (
section 8.7 "Parameter data" on page 31).
When the switch position “9” is selected, additional temperature ranges and alloys can be set through the ROPEX
visualisation software (
section 8.12 "USB interface for visualisation software ROPEXvisual
®
" on page 46).
7.2.3
Configuration of the station address
On these two rotary coding switches, the station address of the UPT-6006 can be set in the PROFIBUS network
from 1 to 99. Changes do not become effective until after switch-on.
With the switch setting 00, the station address with a class 2 master can be set over PROFIBUS with the SSA
service (set slave address). If no address has been assigned, the device has the standard address 126. The
address assigned through SSA remains stored in the device. As soon as a station address not equal to 00 is set
on the rotary coding switches and the 24 VDC power supply of the UPT-6006 is switched off and back on again,
the stored address assigned through SSA is erased and the controller uses the set station address. In switch set-
ting 00, the standard address is then 126 again.
With the help of address setting via the rotary coding switch, it is possible to carry out a device change in an
existing machine without a programming tool. Only the same setting of the rotary coding switch can be made in
the replacement device.
Rotary encoder switch
Station address
00
Changeable through SSA in the range 0…126
01…99
• Fixed address in the range 1…99
• Stored address is reset to 126
0
5
1
2
3
4
6
7
8
9
AUX
CONF
IG
URA
TIO
N
ALARM
OU
TP
UT
ENER
GIZ
ED
(
)
AT
ALARM
-
DEE
NE
RG
IZ
ED
SWIT
CH
PO
S
.
4
0
9
TE
MP
RANGE
.
500°
C
300°
C
PC
CON
FIG
UR
AT
IO
N
1700
pp
m/K
1700
pp
m/K
(
)
CIR
US
(
)
CIR
US
0
5
1 2
3
4
6
7
8
9
Switch
position
0
4
300°C
500°C
1700ppm/K
1700ppm/K
(CIRUS)
(CIRUS)
Temp.
range
Temp.
coefficient
Heating element
alloy
0 = Factory settings
9
PC-CONFIGURATION
TEM
P . C
OE
FFIC
IEN
T
!
0
0
0
0
5
5
5
5
1
1
1
1
2
2
2
2
3
3
3
3
4
4
4
4
6
6
6
6
7
7
7
7
8
8
8
8
9
9
9
9
PROFIBUS
STATION ADDRESS
x 1
x 10
Station address in PROFIBUS network between
0 and 99.
01 = Factory setting
Содержание CIRUS UPT-6006