Device functions
Version 1
UPT-6006
Page 31
8.7
Parameter data
The parameter data contain values for selection of the heating element alloy, the temperature range, the lower
and upper tolerance band limit for temperature monitoring, the calibration temperature, the measurement impulse
duration (only for special applications), as well as the optional heating time limit. They are transmitted at every
system start from the PROFIBUS master to the UPT-6006. In addition, the parameters can be sent through acy-
clical write/read services at any time from the PROFIBUS master to the controller or queried by the controller. The
DPV1 protocol extensions are required for this. Saving in the UPT-6006 does not take place. The parameter data
have the following structure:
No.
Function
Standard value
1
Possible values
0…3
Reserved
-
-
4
Temperature range / alloy
10
0, 4, 9, 10, 11
5
Lower threshold for temperature OK
10 K
3…99 K
6
Upper threshold for temperature OK
10 K
3…99 K
7
Calibration temperature
20 °C
-1, 0…40 °C
8
Heating time limit (100 ms units)
0
0…99
(0…9.9 s)
9
Expanded device diagnosis
Activated
Deactivated,
Activated
10
Measurement impulse duration
17
17…30
(1.7…3.0 ms)
11
Data format
High/Low Byte
(Intel)
High/Low Byte (Intel),
Low/High Byte (Motorola)
12
Correction factor, channel 0
100%
25…200%
13/14
Maximum start temperature
100 °C
20…500 °C
15
Error number format
10-Bit
4-Bit, 10-Bit
16/17
Temperature coefficient
1700 ppm/K
400…4000 ppm/K
18
Temperature range
300 °C
200, 300, 400, 500 °C
19/20
Maximum temperature
300 °C
200…500 °C
21
Temperature diagnosis
Deactivated
Deactivated, activated
22/23
Temperature diagnosis delay (10 ms units)
0 s
0…999
(0…9.99 s)
24/25
Heat-up time monitoring (10 ms units)
0 s
0…999
(0…9.99 s)
26
Temperature OK bit
Active when
ACTUAL=SET-
POINT
Off,
Active when
ACTUAL=SETPOINT
Active when
ACTUAL=SETPOINT with
latch