Device functions
Page 50
UPT-6006
Version 1
Part 1 of 3: Error messages (malfunctions)
NOTE:
The specified error messages are output as malfunctions (actual value output emits constant error
voltage; alarm LED is continuously lit; alarm relay is active).
Error no.
Actual
value
output
Voltage
[V]
Cause
Measure if initial start-
up
Measure if machine in
operation, heating ele-
ment not changed
1
101
0.66
Current signal missing
Error range
Error range
2
102
1.33
Voltage signal missing
Error range
Error range
3
103
2.00
Voltage and current signals
missing
Error range
Error ranges
4
107
2.66
Temperature jump down-
ward
Error ranges
(“Loose connection”)
Error ranges
(“Loose connection”)
108
Temperature jump upward
307
Temperature too low/high
(
chap. 8.7.12)
-
-
308
309
310
5
201
3.33
Network frequency missing/
fluctuates
Check network
Check network
202
Network frequency too large/
fluctuates
203
Network frequency too
small/fluctuates
6
304
4.00
Heat-up time too long
(
chap. 8.7.13)
Perform
RESET
Perform
RESET
305
Start temperature too high
(
section 8.7.11)
7
901
4.66
Network voltage/synchro-
nising signal missing
Replace device
Replace device
913
Triac defective
Replace device
Replace device
914
Int. error, device defective
Replace device
Replace device
915
916
917
Slide switch for alarm output
incorrect
Check slide switch
Check slide switch
918