Device functions
Version 1
UPT-6006
Page 37
The “Heat-up time monitoring” function must be released for use in the parameter data (
section 8.7 "Parameter
data" on page 31) or through the DPV1 protocol expansion (
section 8.8 "DPV1 protocol expansions" on
page 39) (standard setting: Heating time monitoring off).
8.7.14 Hold mode
Output of the ACTUAL temperature via the PROFIBUS protocol can be parameterised as follows through the
parameter data (GSD file) or the DPV1 protocol expansion:
1.
“Off” (factory setting)
The current ACTUAL temperature is always output in real time.
2.
“On”
The same ACTUAL temperature that was current at the end of the last sealing phase is output. After the con-
troller is switched on, the real ACTUAL temperature is displayed until the end of the first heating phase.
3.
“2 sec.”
This causes the current ACTUAL temperature to be output over the PROFIBUS protocol for an additional
2 seconds at the end of a sealing phase. Then the ACTUAL temperature is output in real time – until the end
of the next sealing phase.
The Hold mode only affects output of the ACTUAL temperature over the PROFIBUS protocol and the numeric tem-
perature display in the ROPEX visualisation software. Output of the ACTUAL temperature over the analogue
output of the controller or the graphic drawing in the ROPEX visualisation software is not changed by this.
Set
95% of set
ACTUAL temperature
Time
Heatup time
Error code
304
Time-
out