Device functions
Page 40
UPT-6006
Version 1
With the DPV1 protocol expansion, there is the possibility to change these settings and functions during operation
of the controller. As a result, the temperature coefficient for the heating band can be adjusted through the PLC
controller during the validation process, for example.
The parameters of the controller can be both read and written over this acyclical service. Access to the parameter
data is made directly over slot index addressing. As the controller does not store the parameters transmitted to it,
after a restart of the controller or bus, it must be ensured that the parameters which were changed from the static
configuration are retransmitted again.
Clarify with the manufacturer how the used PLC system supports the DPV1 protocol expansion.
DPV1 parameter table of the UPT-6006
Standard values are printed in
bold/italics
Slot
Index
Parameter
Range of values
0
255
I&M functions
Article number, serial number, ver-
sion numbers, manufacturer ID
0
0
Cyclic data
section 8.4 "PROFIBUS protocol"
on page 21
1
4
Alloy/range
0: 1700 ppm/K, 300 °C
4: 1700 ppm/K, 500 °C
9: PC configuration
10: Rotary encoder switch
11: variable
1
5
Lower temperature threshold [K]
3…99
(
10
)
1
6
Upper temperature threshold [K]
3…99
(
10
)
1
7
Calibration temperature [°C],
channel 0
-1: variable over cyclical data
0…40
(
20
)
1
8
Heating time limit [0.1 s]
0…99
(
0=No limit
)
1
9
Device diagnosis
0: Deactivated
1: Activated
1
10
Measurement impulse duration
[0.1 ms]
17…30
(
17
)
1
11
Data format
0: Intel
1: Motorola
1
12
Correction factor [%], channel 0
25…200%
(
100
)
1
13
Maximum start temperature [°C]
20…500
(
100
)
1
15
Error number format
0: 4-Bit (2 digit)
1
: 10-Bit (4 digit)
1
16
Temperature coefficient [ppm/K],
channel 0
400…4000
(
1700
)
1
18
Temperature range
0: 200 °C
1: 300 °C
2: 400 °C
3: 500 °C
!