Program parameter 3:
Specifying the nominal thickness of the sheet to be measured.
Fig. 63: Adjusting the nominal thickness
Here the nominal thickness of the sheet to be measured is specified. Normally, the nominal
thickness is the sheet thickness used for teach-in.
Note
A change of the nominal thickness deletes the values determined
during teach-in. A new teach-In is required.
Program parameter 4:
Setting the percentage threshold of the upper limit value.
Fig. 64: Adjusting the upper limit
Value range: between 100% and 150%, with simultaneously displaying the absolute limit value.
The maximal settable absolute limit depends on the sensor:
• P42, P42A:
5 mm (.197 in.)
• P30, P36:
3 mm (.118 in.)
• P75:
6,8 mm (.268 in.)
• P75V:
9,2 mm (.362 in.)
• P128:
14 mm (0.551 in.)
Program parameter 5:
Setting the percentage threshold of the lower limit value.
Fig. 65: Adjusting the lower limit
Value range: between 0% and 99%, with simultaneously displaying the absolute limit value.
program param. 3
nom. thick.: 0.90mm
program param. 4
up 150% 1.350 mm
program param. 5
low: 50% 0.450 mm