with integrated fieldbus interface
Communication with the PLC
B0046191 / Rev. 1.12
74
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
6.2
Data transmission communication
Currently the R1000 uses an I/O configuration for the cyclical data exchange with the master. This
means that for each transmission direction 1 parameter channel (8 Byte) as well as one process
channel has been provided. In contrast to the E10 (4 Byte) with the E20
16 byte
for the process
channel are used.
The following table shows the layout of the communication facility:
Master
Data direction
Input
Data direction
R1000
–> Byte
E0
Paramete
r
cha
nnel
–>
–> Byte
E1
–>
–> Byte
E2
–>
–> Byte
E3
–>
–> Byte
E4
–>
–> Byte
E5
–>
–> Byte
E6
–>
–> Byte
E7
–>
–> Byte
E8
Process chan
nel
–>
–> Byte
E9
–>
–> Byte
E10
–>
–> Byte
E11
–>
–> Byte
E12
–>
–> Byte
E13
–>
–> Byte
E14
–>
–> Byte
E15
–>
–> Byte
E16
–>
–> Byte
E17
–>
–> Byte
E18
–>
–> Byte
E19
–>
–> Byte
E20
–>
–> Byte
E21
–>
–> Byte
E22
–>
–> Byte
E23
–>
Data direction
Output
Data direction
<– Byte
S0
Paramete
r
cha
nnel
<–
<– Byte
S1
<–
<– Byte
S2
<–
<– Byte
S3
<–
<– Byte
S4
<–
<– Byte
S5
<–
<– Byte
S6
<–
<– Byte
S7
<–
<– Byte
S8
Process chan
nel
<–
<– Byte
S9
<–
<– Byte
S10
<–
<– Byte
S11
<–
<– Byte
S12
<–
<– Byte
S13
<–
<– Byte
S14
<–
<– Byte
S15
<–
<– Byte
S16
<–
<– Byte
S17
<–
<– Byte
S18
<–
<– Byte
S19
<–
<– Byte
S20
<–
<– Byte
S21
<–
<– Byte
S22
<–
<– Byte
S23
<–
The R1000 is controlled by the process channel and via the parameter channel all systems and
program data are accessible.
Pos: 49 /Doppelblech/Geräte/E20 Bus/6 Kommunikation mit der SPS/Prozesskanal @ 0\mod_1173436313359_501.docx @ 3349 @ 2333333332333333333 @ 1