2-18
Programming and Parameters
D
Y
NAMIC CO
NTR
O
L
Stop/
Brak
e Mode
s
159
[DC Brake Time]
Sets the amount of time DC brake current
is “injected” into the motor.
Default:
Min/Max:
Units:
0.0 Secs
0.0/90.0 Secs
0.1 Secs
thru
160
[Bus Reg Ki]
Sets the responsiveness of the bus
regulator.
Default:
Min/Max:
Units:
30
0/5000
1
161
162
[Bus Reg Mode A]
[Bus Reg Mode B]
Sets the method and sequence of the DC
bus voltage regulator. Choices are
dynamic brake, frequency adjust or both.
Options 2 & 3 only appear when a
dynamic brake is installed in the drive.
Dynamic Brake Setup
If a dynamic brake resistor is connected
to the drive, both of these parameters
must be set to either option 2 or 3.
Refer to the Attention statement on page
for important information on bus
regulation.
Default:
Options:
1
0
0
1
2
3
“Adjust Freq”
“Disabled”
“Disabled”
“Adjust Freq”
“Dynamic Brak”
“Both-DB 1st”
163
[DB Resistor Type]
Selects whether an external DB resistor
will be used.
Note: Used for frame 9 drives only.
Default:
Options:
0
0
1
“None”
“None”
“External Res”
164
[Bus Reg Kp]
Proportional gain for the bus regulator.
Used to adjust regulator response.
Default:
Min/Max:
Units:
610
0/10000
1
165
[Bus Reg Kd]
Derivative gain for the bus regulator. Used
to control regulator overshoot.
Default:
Min/Max:
Units:
122
0/10000
1
Res
tar
t Mode
s
167
[Powerup Delay]
Defines the programmed delay time, in
seconds, before a start command is
accepted after a power up.
Default:
Min/Max:
Units:
0.0 Secs
0.0/30.0 Secs
0.1 Secs
168
[Start At PowerUp]
Enables/disables a feature to issue a
Start or Run command and automatically
resume running at commanded speed
after drive input power is restored.
Requires a digital input configured for Run
or Start and a valid start contact.
Default:
Options:
0
0
1
“Disabled”
“Disabled”
“Enabled”
File
Gr
oup
No.
Parameter Name & Description
Values
Related
!
ATTENTION:
The drive does not offer protection for externally
mounted brake resistors. A risk of fire exists if external braking
resistors are not protected. External resistor packages must be
self-protected from over temperature or the protective circuit shown
in
(or equivalent) must be supplied.
!
ATTENTION:
Equipment damage and/or personal injury may result
if this parameter is used in an inappropriate application. Do not use
this function without considering applicable local, national and
international codes, standards, regulations or industry guidelines.
Содержание powerflex 700h
Страница 1: ...PROGRAMMING MANUAL High Power Firmware Versions x xxx 3 001 PowerFlex 700H AC Drives ...
Страница 10: ...P 4 Overview Notes ...
Страница 56: ...2 42 Programming and Parameters Notes ...
Страница 70: ...3 14 Troubleshooting Notes ...
Страница 103: ......