2-16
Programming and Parameters
Dynamic Control File
SPEED COMMAN
D
Pr
oc
ess
PI/T
rim
138
[PI Output Meter]
Present value of the PI output.
Default:
Min/Max:
Units:
Read Only
–/+100.0 Hz
–/+100.0%
0.1 Hz
0.1%
thru
460
[PI Reference Hi]
Scales the upper value of [PI Reference
Sel] of the source.
Default:
Min/Max:
Units:
100.0%
–/+100.0%
0.1%
461
[PI Reference Lo]
Scales the lower value of [PI Reference
Sel] of the source.
Default:
Min/Max:
Units:
–100.0%
–/+100.0%
0.1%
462
[PI Feedback Hi]
Scales the upper value of [PI Feedback]
of the source.
Default:
Min/Max:
Units:
100.0%
–/+100.0%
0.1%
463
[PI Feedback Lo]
Scales the lower value of [PI Feedback] of
the source.
Default:
Min/Max:
Units:
0.0%
–/+100.0%
0.1%
464
[PI Output Gain]
Sets the gain factor for [PI Output Meter].
Note: Added for firmware version 3.001.
Default:
Min/Max:
Units:
1.000
–/+8.000
0.001
File
Gr
oup
No.
Parameter Name & Description
Values
Related
File
Gr
oup
No.
Parameter Name & Description
Values
Related
D
Y
NA
MIC
CON
T
R
O
L
Ra
mp R
at
es
140
141
[Accel Time 1]
[Accel Time 2]
Sets rate of accel for all speed increases.
Default:
Min/Max:
Units:
10.0 Secs
10.0 Secs
0.1/3276.7 Secs
0.1 Secs
thru
142
143
[Decel Time 1]
[Decel Time 2]
Sets rate of decel for all speed decreases.
Default:
Min/Max:
Units:
10.0 Secs
10.0 Secs
0.1/3276.7 Secs
0.1 Secs
thru
146
[S Curve %]
Sets the percentage of accel or decel time
that is applied to the ramp as S Curve.
Time is added, 1/2 at the beginning and 1/
2 at the end of the ramp.
Default:
Min/Max:
Units:
0%
0/100%
1%
thru
Load Li
mits
147
[Current Lmt Sel]
Selects the source for the adjustment of
current limit (i.e. parameter, analog input,
etc.).
Default:
Options:
0
0
1
2
“Cur Lim Val”
“Cur Lim Val”
“Analog In 1”
“Analog In 2”
148
[Current Lmt Val]
Defines the current limit value when
[Current Lmt Sel] = “Cur Lim Val.”
Default:
Min/Max:
Units:
[Rated Amps]
×
1.5
(Equation yields approxi-
mate default value.)
Based on Drive Rating
0.1 Amps
Max Speed
Accel Time
Accel Rate
=
Max Speed
Decel Time
Decel Rate
=