[Sleep Wake Mode]
Enables/disables the Sleep/Wake
function.
Important:
When enabled, the
following conditions must be met:
•
A proper minimum value must be
programmed for [Sleep Level].
•
A speed reference must be selected in
[Speed Ref A Sel].
•
At least one of the following must be
programmed (and input closed) in
[Digital Inx Sel]; “Enable,” “Stop=CF,”
“Run,” “Run Forward,” “Run Reverse.”
Note: Option 2 was added for firmware
version 2.001.
Default:
Options:
0
0
1
2
“Disabled”
“Disabled”
“Direct” (Enabled)
“Invert”
(1)
When power is cycled, if all conditions are present after power is restored, restart will
occur.
(2)
The drive only starts after Sleep Wake Mode is “enabled” and a valid signal is received.
(3)
The active speed reference is determined as explained in “Reference Control” in the
Installation Manual. The Sleep/Wake function and the speed reference may be
assigned to the same input.
(4)
Command must be issued from HIM, TB or network.
(5)
Run Command must be cycled.
(6)
Signal does not need to be greater than wake level.
179
[Sleep Wake Ref]
Selects the source of the input controlling
the Sleep Wake function.
Default:
Options:
2
1
2
3-6
“Analog In 2”
“Analog In 1”
“Analog In 2”
“Reserved”
180
[Wake Level]
Defines the analog input level that will
start the drive.
Default:
Min/Max:
Units:
6.000 mA, 6.000 Volts
[Sleep Level]/20.000 mA
10.000 Volts
0.001 mA
0.001 Volts
181
[Wake Time]
Defines the amount of time at or above
[Wake Level] before a Start is issued.
Default:
Min/Max:
Units:
0.0 Secs
0.0/1000.0 Secs
0.1 Secs
File
Gr
oup
No.
Parameter Name & Description
Values
Related
!
ATTENTION:
Enabling the Sleep Wake function can cause
unexpected machine operation during the Wake mode. Equipment
damage and/or personal injury can result if this parameter is used
in an inappropriate application. Do Not use this function without
considering the table below and applicable local, national &
international codes, standards, regulations or industry guidelines.
Conditions Required to Start Drive
Input
After Power-Up After a Drive Fault
After a Stop Command
Reset by Stop-CF,
HIM or TB
Reset by Clear
Faults (TB)
HIM or TB
Stop
Stop Closed
Wake Signal
Stop Closed
Wake Signal
New Start or Run Cmd.
Stop Closed
Wake Signal
Stop Closed
Analog Sig. > Sleep Level
New Start or Run Cmd.
Enable
Enable Closed
Wake Signal
Enable Closed
Wake Signal
New Start or Run Cmd.
Enable Closed
Wake Signal
Enable Closed
Analog Sig. > Sleep Level
New Start or Run Cmd.
Run
Run For.
Run Rev.
Run Closed
Wake Signal
New Run Cmd.
Wake Signal
Run Closed
Wake Signal
New Run Cmd.
Wake Signal