[PI Reference Sel]
Selects the source of the PI reference.
Default:
Options:
0
0
1
2
3-8
9
10
11-17
18-22
“PI Setpoint”
“PI Setpoint”
“Analog In 1”
“Analog In 2”
“Reserved”
“MOP Level”
“Master Ref”
“Preset Spd1-7”
“DPI Port 1-5”
thru
127
[PI Setpoint]
Provides an internal fixed value for
process setpoint when [PI Reference Sel]
is set to “PI Setpoint.”
Default:
Min/Max:
Units:
50.0%
–/+100.0% of Maximum
Process Value
0.1%
thru
128
[PI Feedback Sel]
Selects the source of the PI feedback.
Default:
Options:
2
“Analog In 2”
.
thru
129
[PI Integral Time]
Time required for the integral component
to reach 100% of [PI Error Meter]. Not
functional when the PI Hold bit of [PI
Control] = “1” (enabled).
Default:
Min/Max:
Units:
2.0 Secs
0.00/100.00 Secs
0.01 Secs
thru
130
[PI Prop Gain]
Sets the value for the PI proportional
component.
PI Error x PI Prop Gain = PI Output
Default:
Min/Max:
Units:
1.0
0.00/100.00
0.01
thru
131
[PI Lower Limit]
Sets the lower limit of the PI output.
Default:
Min/Max:
Units:
–[Maximum Freq]
100%
–/+800.0%
0.1%
thru
132
[PI Upper Limit]
Sets the upper limit of the PI output.
Default:
Min/Max:
Units:
+[Maximum Freq]
100%
–/+800.0%
0.1%
thru
133
[PI Preload]
Sets the value used to preload the
integral component on start or enable.
Default:
Min/Max:
Units:
0.0 Hz
100%
–/+800.0%
0.1%
thru
134
[PI Status]
Status of the Process PI regulator.
Read Only
thru
135
[PI Ref Meter]
Present value of the PI reference signal.
Default:
Min/Max:
Units:
Read Only
–/+100.0%
0.1%
thru
136
[PI Fdback Meter]
Present value of the PI feedback signal.
Default:
Min/Max:
Units:
Read Only
–/+100.0%
0.1%
thru
137
[PI Error Meter]
Present value of the PI error.
Default:
Min/Max:
Units:
Read Only
–/+100.0%
0.1%
thru
File
Gr
oup
No.
Parameter Name & Description
Values
Related
0
0
0
0
x
x
x
x
x
x
x
x
x
x
x
x
10
0
1
2
3
4
5
6
7
8
9
11
12
13
14
15
1
= Condition True
0
= Condition False
x = Reserved
Bit #
PI Enab
led
PI Hold
PI Reset
PI InLimit
Содержание powerflex 700h
Страница 1: ...PROGRAMMING MANUAL High Power Firmware Versions x xxx 3 001 PowerFlex 700H AC Drives ...
Страница 10: ...P 4 Overview Notes ...
Страница 56: ...2 42 Programming and Parameters Notes ...
Страница 70: ...3 14 Troubleshooting Notes ...
Страница 103: ......