CABINET HEATER
9.5
M
ain Fan Circuit
(Single Phase)
Note:
Direct drive fans are normally changed as a complete assembly to ensure correct fan balancing.
NO
NO
NO
Check for 230v
at terminals 1 to N
Main fan will not operate
following warm up
period of heat exchanger
Press in white button
of fan/limit thermostat
and retest.
Re check supply to
terminals L1 to N
Fault lies elsewhere
Check the setting of the
fan thermostat as in
Section 5.1
Check calibration of the
fan thermostat.
The dial should indicate
the approximate
temperature of the
sampled air.
Fan thermostat faulty.
Replace and reset.
Check and test wiring to
motor.
Does the motor run now ?
Motor faulty.
Replace complete fan
unit.
Thermal overload in motor
is faulty.
Replace complete fan
unit.
Motor stops after running
some time.
MOTOR RUNNING
NO
YES
YES
YES
NO
YES
YES
NO
YES
Содержание Combat HF 30 v4
Страница 2: ......
Страница 47: ...Page 45 CABINET HEATER Section 6 Wiring Diagrams Fig 6 1 As Wired Diagram for Models 015 to 030 Floor Standing ...
Страница 48: ...Page 46 CABINET HEATER Fig 6 2 As Wired Diagram for Models 015 to 030 Horizontal Mounting ...
Страница 49: ...Page 47 CABINET HEATER Fig 6 3 As Wired Diagram for Models 040 and 050 Floor Standing ...
Страница 50: ...Page 48 CABINET HEATER Fig 6 4 As Wired Diagram for Models 040 050 Horizontal Mounting ...
Страница 51: ...Page 49 CABINET HEATER Fig 6 5 As Wired Diagram for Models 060 to 0100 Floor Standing ...
Страница 52: ...Page 50 CABINET HEATER Fig 6 6 As Wired Diagram for Models 060 to 0100 Horizontal Mounting ...
Страница 55: ...Page 55 CABINET HEATER Fig 6 12 Wiring Diagram for High Flow Models HF40 v3 HF50 v2 HF50 v3 and HF50 v4 ...