Page 18
CABINET HEATER
2.4
Honeywell Combination Fan/Limit Thermostat
This is a dual function control and safety device:
1.
Fan Thermostat.
This automatically turns the fan ON and OFF during the heater operation controlled by the
leaving air temperature. It is fitted with a white manual override button which must be in its pulled out position for
automatic operation. In its pushed in position the fan(s) will run continuously.
2. Limit Thermostat.
This protects the heater from overheating caused by a reduction of air flow over the heat
exchanger. It is a manual reset device and once operated prevents the heater restarting until reset.
To reset wait until the heater has cooled sufficiently then press in and release the red reset button. After operation of the
limit thermostat, efforts should be made to locate the problem causing its operation.
Note
: IT IS ESSENTIAL THAT THE LINK SHOWN IN FIG. 2.3 IS REMOVED IN THE EVENT OF A REPLACEMENT
COMBINATION FAN/LIMIT THERMOSTAT BEING FITTED
Following replacement or adjustment, the limit thermostat setting must be re-sealed using a suitable paint spot seal.
For settings see Commissioning Section 5.1.2.1.
Fig. 2.3
Combination Fan/Limit Thermostat
2.3.8
Main Gas Valve
(For models above 030)
Ten seconds from when the start gas is energised the main gas valves energise and the main flame expands from the
start gas. The control is now in its normal run position.
When the external controls are satisfied the control box turns off all outputs simultaneously and returns to rest position
for the beginning of the next sequence.
2.3.9
Fault Conditions
If at any stage the flame fails , the air pressure switch detects a loss of air pressure or a rise in combustion chamber
pressure ,then the control will go to lockout. The red light on the control box will glow and the control will need to be
manually reset before any further start attempt can be made.
For control sequence see Fig. 2.2.
Содержание Combat HF 30 v4
Страница 2: ......
Страница 47: ...Page 45 CABINET HEATER Section 6 Wiring Diagrams Fig 6 1 As Wired Diagram for Models 015 to 030 Floor Standing ...
Страница 48: ...Page 46 CABINET HEATER Fig 6 2 As Wired Diagram for Models 015 to 030 Horizontal Mounting ...
Страница 49: ...Page 47 CABINET HEATER Fig 6 3 As Wired Diagram for Models 040 and 050 Floor Standing ...
Страница 50: ...Page 48 CABINET HEATER Fig 6 4 As Wired Diagram for Models 040 050 Horizontal Mounting ...
Страница 51: ...Page 49 CABINET HEATER Fig 6 5 As Wired Diagram for Models 060 to 0100 Floor Standing ...
Страница 52: ...Page 50 CABINET HEATER Fig 6 6 As Wired Diagram for Models 060 to 0100 Horizontal Mounting ...
Страница 55: ...Page 55 CABINET HEATER Fig 6 12 Wiring Diagram for High Flow Models HF40 v3 HF50 v2 HF50 v3 and HF50 v4 ...