Page 12
CABINET HEATER
Table 2.5 Ecoflam ON/OFF LPG (G31) with Dungs Valve, Burner Reference C
Data for all versions "H" horizontal, "HF" high flow
Gas rates corrected to standard conditions 1013.25 mbar 15°C
HEAD SETTING
- See Adjustment Of The Firing Head in Ecoflam Instructions
INLET PRESSURE 37 mbar
(MINIMUM 25 mbar , MAXIMUM 45 mbar)
MODEL
PGP 015 PGP 020 PGP 030 PGP 040 PGP 050 PGP 060 PGP 070 PGP 080 PGP 0100
Gross heat Input
(kW)
56.1
73.7
103
144.7
182.1
220
253.6
297
363
Net heat Input
(kW)
51
67
93.6
131.5
165.5
200
230.5
270
330
Approx heat output
(kW)
46.9
60.3
81.9
114.7
144.8
176.0
202.8
237.6
290.1
Main Gas Orifice
(mm dia.)
8.5
10.0
10.0
14.5
14.5
14.5
14.5
14.5
Start Gas Orifice
(mm dia.)
5.0
6.0
7.0
7.0
7.0
7.0
Max Gas Rate
(m
3
/hr)
2.10
2.70
3.80
5.40
6.80
8.20
9.40
11.00
13.50
(kg/hr)
3.9
5.1
7.1
10.1
12.7
15.4
17.6
20.6
25.3
Lt/hr
7.7
10.0
13.9
19.8
25.0
30.3
34.6
40.5
49.7
Main Burner Gas Pressure
(mbar)
3.9
3.1
5.6
4.6
7.0
5.2
6.8
9.5
7.6
Start Gas Pressure
(mbar)
1.6
2.5
0.8
1.0
1.5
3.1
BURNER TYPE
AZUR
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
60 AH
120 AH
120 AH
170 AH
250R AH 250 AH
250 AH
250S AH
350 AH
Burner Head
s
s
s
s
s
s
s
s
s
Burner Injector
LPG
Head Setting
(mm)
10.0
13.0
15.0
14
24.0
24.0
24.0
20.0
1st Flame Air Setting
number
3.8
3.5
6.0
3.5
4.5
3.5
4.7
1.7
3.0
2nd Flame Air Setting
Gas Valve Setting
Valve Type
MBDLE
MBDLE
MBDLE
MBDLE
MBDLE
MBDLE
MBDLE
MBDLE
MBDLE
Main Gas
405
405
405
407
410
410
410
410
412
Valve Type
S
S
S
S
S
S
Start Gas
0 832 051 0 832 051 0 832 051 0 832 051 0 832 051 0 832 051
AIR PRESSURE SWITCH
SETTING (mbar)
3.8
4.5
5.9
2.9
5.5
3.6
4.5
6.8
5.1
Max flue static pressure
norm. flue static pressure
(mbar)
-0.05
-0.05
-0.09
-0.30
-0.05
-0.25
-0.17
0.10
0.45
Gas Connection
3/4"
3/4"
3/4"
3/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
S.= S I T
H.= HONEYWELL
Содержание Combat HF 30 v4
Страница 2: ......
Страница 47: ...Page 45 CABINET HEATER Section 6 Wiring Diagrams Fig 6 1 As Wired Diagram for Models 015 to 030 Floor Standing ...
Страница 48: ...Page 46 CABINET HEATER Fig 6 2 As Wired Diagram for Models 015 to 030 Horizontal Mounting ...
Страница 49: ...Page 47 CABINET HEATER Fig 6 3 As Wired Diagram for Models 040 and 050 Floor Standing ...
Страница 50: ...Page 48 CABINET HEATER Fig 6 4 As Wired Diagram for Models 040 050 Horizontal Mounting ...
Страница 51: ...Page 49 CABINET HEATER Fig 6 5 As Wired Diagram for Models 060 to 0100 Floor Standing ...
Страница 52: ...Page 50 CABINET HEATER Fig 6 6 As Wired Diagram for Models 060 to 0100 Horizontal Mounting ...
Страница 55: ...Page 55 CABINET HEATER Fig 6 12 Wiring Diagram for High Flow Models HF40 v3 HF50 v2 HF50 v3 and HF50 v4 ...