Page 14
CABINET HEATER
Table 2.7
Ecoflam HIGH/LOW or MODULATING Burner with Dungs Valve
Burner Reference "H" L.P.G. G31
Data for all versions "H" horizontal, "HF" high flow
Gas rates corrected to standard conditions 1013.25 mbar 15°C
INLET PRESSURE 37 m bar (m inim um 25m bar, m axim um 45m bar)
M O DEL
PGP 015
PGP 020
PGP 030
PGP 040
PGP 050
PG P 060
PG P 070
PG P 080
PG P 0100
Maxim um Gross heat Input
(kW )
55.0
74.0
104.0
145.9
183.0
221.0
256.0
300.0
367.0
Maxim um Net heat Input
(kW )
49.6
66.7
93.7
131.5
164.9
199.1
230.7
270.3
330.7
Minim um Gross heat Input
(kW )
33.85
44.40
63.82
87.13
109.88
133.19
153.16
179.80
219.76
Minim um net heat Input
(kW )
30.50
40.00
57.50
78.50
99.00
120.00
138.00
162.00
198.00
Approx heat output (Net)
(kW )
43.5
58.5
82.2
115.3
144.6
174.6
202.0
237.0
289.9
Main Gas Orifice
(m m dia.)
8.5
10.0
10.0
14.5
14.5
14.5
14.5
14.5
N/A
Start Gas Orifice
(m m dia.)
7.0
7.0
7.0
7.0
7.0
7.0
Max Gas Rate
(Sm 3/hr)
2.11
2.73
3.70
5.50
6.89
8.32
9.30
11.00
12.40
Min Gas Rate
(Sm 3/hr)
1.30
1.65
2.31
3.28
4.19
4.99
5.73
6.68
7.98
Main Burner G as Pressure
(m bar)
4.3
5.4
5.2
3.9
7.5
6.0
7.5
10.1
5.7
Min. Burner G as Pressure
(m bar)
1.7
2.2
1.2
1.5
1.9
1.9
2.0
2.7
1.5
Start Gas Pressure
(m bar)
1.1
1.7
0.6
0.7
0.7
1.5
BURNER TYPE
AZUR
BLU
BLU
BLU
BLU
BLU
BLU
BLU
BLU
60
120
120
170
250R
250
250
250
350
Burner Head
s
s
s
s
s
s
s
s
s
Burner Injector
LPG
Head Setting
(m m )
0.0
8.0
10.0
15.0
14
T.O.
T.O.
T.O.
T.O.
Low Flam e Air Orange Cam
**
20°
13°
22°
18°
18°
18°
22°
25°
25°
High Flam e Air Red Cam
**
33°
40°
80°
30°
32°
30°
35°
55°
60°
Gas Valve Setting
0-1,4
0,3-0,9
0-1,1
0-1,1
0-1,1
0-1,4
0-1,4
0-1,5
0-0,85
Valve Type
MBVEF
MBVEF
MBVEF
MBVEF
MBVEF
MBVEF
MBVEF
MBVEF
MBVEF
Main Gas
407
407
407
407
412
412
412
412
412
Valve Type
S.I.T.
S.I.T.
S.I.T.
S.I.T.
S.I.T.
S.I.T.
Start Gas
832051
832051
832051
832051
832051
832051
AIR PRESSURE SW ITCH
SETTING (m bar)
1.5
1.5
1.5
1.0
1.5
1.5
1.5
2.0
2.5
Max flue static pressure
norm . flue static pressure
(m bar)
-0.05
-0.05
-0.09
-0.30
-0.05
-0.25
-0.17
0.10
0.45
Gas Connection
3/4"
3/4"
3/4"
3/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
1 1/4"
S.= STANDARD
** Note the air setting is a guide only, the final setting is subject to the com bustion testing.
HEAD SETTING
- See Adjustment Of The Firing Head in Ecoflam Instructions
When setting the minimum firing rate a check must be made following the setting of the burner combustion .
The check is made by running the heater on low fire for a minimum of 15 minutes at the full transport air rate and at
typical ambient conditions. During the test check that the flue gas temperature does not fall below 150°C .Should the
flue gas temperature fall below 150°C then the low fire gas setting must be increased to a value that will achieve 150°C
flue gas temperature, otherwise condensation may form in the heat exchanger and flue causing rapid corrosion and
short operational life.
Содержание Combat HF 30 v4
Страница 2: ......
Страница 47: ...Page 45 CABINET HEATER Section 6 Wiring Diagrams Fig 6 1 As Wired Diagram for Models 015 to 030 Floor Standing ...
Страница 48: ...Page 46 CABINET HEATER Fig 6 2 As Wired Diagram for Models 015 to 030 Horizontal Mounting ...
Страница 49: ...Page 47 CABINET HEATER Fig 6 3 As Wired Diagram for Models 040 and 050 Floor Standing ...
Страница 50: ...Page 48 CABINET HEATER Fig 6 4 As Wired Diagram for Models 040 050 Horizontal Mounting ...
Страница 51: ...Page 49 CABINET HEATER Fig 6 5 As Wired Diagram for Models 060 to 0100 Floor Standing ...
Страница 52: ...Page 50 CABINET HEATER Fig 6 6 As Wired Diagram for Models 060 to 0100 Horizontal Mounting ...
Страница 55: ...Page 55 CABINET HEATER Fig 6 12 Wiring Diagram for High Flow Models HF40 v3 HF50 v2 HF50 v3 and HF50 v4 ...