Page 67
CABINET HEATER
10.2.1
Burner Lockout Reset Button
This button which is built into the burner control box will illuminate when the control has gone to safety shut down
lockout.
This may be caused by flame failure.
After lockout has occurred, a waiting time of one minute must be observed before an attempt to reset the control is
made by pressing in the illuminated button.
WARNING
IF THE CONTROL SHOULD GO TO LOCKOUT AGAIN, DO NOT MAKE FURTHER ATTEMPTS AT
RESTARTING THE HEATER UNTIL THE FAULT HAS BEEN TRACED AND REPAIRED BY A COMPETENT
PERSON.
FOR OIL FIRED HEATERS IT SHOULD BE NOTED THAT UNBURNED RESIDUAL OIL IN THE COMBUSTION
CHAMBER IS AN EXPLOSION RISK.
10.2.2
Combination Fan/Limit Thermostat
This is located on the top right hand side of the heater, see Fig. 1.1. This control ensures the heater does not blow cold
air in the normal heating cycle and protects the heat exchanger against overheating.
Although it should not be necessary for the user to touch this control, it is worth noting that:
Pressing in the white button on the combination fan limit thermostat causes the main fan(s) to run continuously.
For normal operation this button should be pulled to the out position.
If for any reason the main fan should fail or the air flow is reduced the built in limit thermostat will cause the burner to go
to safety shut down lockout. This condition will persist until the fault is corrected and the manual reset button is
operated. The combination fan/limit thermostat is located on the right-hand side of the heater and is preset during
commissioning (see 5.1.2.1).
The limit thermostat is a manual reset device. To reset press in and release the red reset button after allowing the
heater to cool.
WARNING
THE MAIN ELECTRICAL ISOLATOR SHOULD ONLY BE USED IN AN EMERGENCY
AND SHOULD NOT BE USED FOR CLOSING DOWN THE BURNER, AS THIS SWITCHES OFF THE
MAIN FAN PREMATURELY AND MAY DAMAGE THE HEAT EXCHANGER, INVALIDATING THE WARRANTY
AND CAUSING A POTENTIAL FIRE HAZARD.
Содержание Combat HF 30 v4
Страница 2: ......
Страница 47: ...Page 45 CABINET HEATER Section 6 Wiring Diagrams Fig 6 1 As Wired Diagram for Models 015 to 030 Floor Standing ...
Страница 48: ...Page 46 CABINET HEATER Fig 6 2 As Wired Diagram for Models 015 to 030 Horizontal Mounting ...
Страница 49: ...Page 47 CABINET HEATER Fig 6 3 As Wired Diagram for Models 040 and 050 Floor Standing ...
Страница 50: ...Page 48 CABINET HEATER Fig 6 4 As Wired Diagram for Models 040 050 Horizontal Mounting ...
Страница 51: ...Page 49 CABINET HEATER Fig 6 5 As Wired Diagram for Models 060 to 0100 Floor Standing ...
Страница 52: ...Page 50 CABINET HEATER Fig 6 6 As Wired Diagram for Models 060 to 0100 Horizontal Mounting ...
Страница 55: ...Page 55 CABINET HEATER Fig 6 12 Wiring Diagram for High Flow Models HF40 v3 HF50 v2 HF50 v3 and HF50 v4 ...