Page 3
CABINET HEATER
Section 1.
General Specification
1.1
General Information - Standard Models
COMBAT® cabinet warm air heaters are self contained units fitted with a packaged burner and are supplied ready for
installation on site to be used with external controls.
The burner controls which form part of the packaged burner are designed for safe operation between
-20°C to 60°C. However the heater should not be operated in ambient temperatures above 32°C .At Ambient temperatures
above 29°C some models may require the maximum heat input to be reduced, seek advice from Roberts-Gordon UK
Ltd. under these circumstances
The standard PGP or POP heater is the free standing model.
Models are available with various options are:
PGPH & POPH models for use in the horizontal (suspended) mode
PGPE & POPE weatherproof models for external siting
HF range of 'High Flow' gas fired and oil fired heaters with higher air flows
PGP/H and HF/H gas fired ranges for Ecoflam high /low burners
PGP/M and HF/M gas fired ranges for Ecoflam fully modulating burners
POP/H and HF/H oil fired ranges are also available with Ecoflam High /Low burners
COMBAT® cabinet heaters are available with heat outputs ranging from 47.3kW to 290kW.
All heaters are fitted with fully automatic 'packaged' forced draught oil fired or gas fired burners manufactured for
Roberts-Gordon UK Ltd.
The heater cabinets are manufactured in Zintec coated mild steel which is finished with a stove cured powder coat
paint.
The combustion chambers are of high grade stainless steel construction. The heat exchangers are mild steel tubular
all welded construction.
Centrifugal fan(s) located in the base of the heater cabinet provide heated recirculation air, which is distributed from the
top of the heater through the fully adjustable louvred outlet heads.
The
fan(s)
are either direct drive or belt driven dependent upon model:
Models 015 - 050 inclusive - Direct Drive (except High Flow)
Models 060 - 0100 inclusive - Belt Drive
The
required electrical supply
is: 230 volt 50Hz single phase on models 015 to 030 and 400 volt 50Hz three phase
and neutral on models 040 to 0100 (Models PGP and POP 040 and 050 are also available as single phase belt drive
to special order). All High Flow models require a 400V, 50Hz, three phase and Neutral electrical supply.
ON/OFF control, temperature control, time control, and frost protection are available as a remote control which needs
to be site wired to afford proper operation of the heater. Alternatively, any remote energy controls may be used which
must be installed in accordance with Section 4.3.
Each heater must be fitted with its own natural draught flue in accordance with local regulations and the instructions in
this booklet.
Fig. 1.1 shows the basic parts of the heater.
Содержание Combat HF 30 v4
Страница 2: ......
Страница 47: ...Page 45 CABINET HEATER Section 6 Wiring Diagrams Fig 6 1 As Wired Diagram for Models 015 to 030 Floor Standing ...
Страница 48: ...Page 46 CABINET HEATER Fig 6 2 As Wired Diagram for Models 015 to 030 Horizontal Mounting ...
Страница 49: ...Page 47 CABINET HEATER Fig 6 3 As Wired Diagram for Models 040 and 050 Floor Standing ...
Страница 50: ...Page 48 CABINET HEATER Fig 6 4 As Wired Diagram for Models 040 050 Horizontal Mounting ...
Страница 51: ...Page 49 CABINET HEATER Fig 6 5 As Wired Diagram for Models 060 to 0100 Floor Standing ...
Страница 52: ...Page 50 CABINET HEATER Fig 6 6 As Wired Diagram for Models 060 to 0100 Horizontal Mounting ...
Страница 55: ...Page 55 CABINET HEATER Fig 6 12 Wiring Diagram for High Flow Models HF40 v3 HF50 v2 HF50 v3 and HF50 v4 ...