Page 41
CABINET HEATER
5.2.4
Adjust Burner Oil Pressure
Adjust the burner oil pressure to the value for model given in the data table for the burner reference letter and burner
manufacturers information for details of the burner oil pump.
When completed turn off burner and remove test gauge and refit port plug.
5.2.5
Set Combustion Air
The combustion air must now be set. This is carried out by measuring the emissions in the flue at a point within one
metre from the outlet of the heater and adjusting for the highest carbon dioxide (CO
2
) levels obtainable, usually 10.5 -
11.5%, whilst making little or no smoke (smoke number 0 -1). Tests must be carried out with all covers fitted and after
the heater has been running for at least 15 minutes.
Closing the combustion air damper (reducing number) will raise both CO
2
and smoke number. Conversely opening the
air damper (rising number) will reduce these levels.
5.2.6
Completion
Recheck and note all results and settings on the commissioning data sheet at the rear of this these instructions. Test
burner for correct start and stop operation, several times. Check that all safety devices operate correctly.
Inspect the heater and pipework for any oil leaks and repair where necessary.
5.2.7
Hand Over
Replace all covers panels or caps removed during commissioning securely. Hand these instructions to the user or
leave them at the heater. Explain to the user the operation of the heater, this should include:
Starting and stopping the heater.
How to set the time switch (where fitted)
How to set the thermostats and their position.
What to do if the heater does not operate.
How to vent air from the fuel system.
How to measure the fuel in the storage tank.
The grade of fuel to be used.
Any other points on the installation that the user may need to know.
Содержание Combat HF 30 v4
Страница 2: ......
Страница 47: ...Page 45 CABINET HEATER Section 6 Wiring Diagrams Fig 6 1 As Wired Diagram for Models 015 to 030 Floor Standing ...
Страница 48: ...Page 46 CABINET HEATER Fig 6 2 As Wired Diagram for Models 015 to 030 Horizontal Mounting ...
Страница 49: ...Page 47 CABINET HEATER Fig 6 3 As Wired Diagram for Models 040 and 050 Floor Standing ...
Страница 50: ...Page 48 CABINET HEATER Fig 6 4 As Wired Diagram for Models 040 050 Horizontal Mounting ...
Страница 51: ...Page 49 CABINET HEATER Fig 6 5 As Wired Diagram for Models 060 to 0100 Floor Standing ...
Страница 52: ...Page 50 CABINET HEATER Fig 6 6 As Wired Diagram for Models 060 to 0100 Horizontal Mounting ...
Страница 55: ...Page 55 CABINET HEATER Fig 6 12 Wiring Diagram for High Flow Models HF40 v3 HF50 v2 HF50 v3 and HF50 v4 ...