59
fUNCtIONS
Control panel
occupation
Water setpoint with direct access to the control panel
field
Water setpoint from the parameter menu
field
Cooling setpoint away
5 - 18°C
Cooling setpoint home [P407] + away cooling offset [P409]
0 - 10°C
HEAtING
Control panel
occupation
Water setpoint with direct access to the control panel
field
Water setpoint from the parameter menu
field
Heating setpoint home
20 - 60°C
Heating setpoint home [P401]
20 - 60°C
Heating setpoint night
20 - 60°C
Heating setpoint home [P401] + Offset heating night [P402]
-10 a 0°C
Heating setpoint away
20 - 60°C
Heating setpoint home [P401] + Offset heating away [P403]
-10 a 0°C
Only DHW ACS (setpoints defined under the change, also setpoints for DHW mode)
Control panel
occupation
Water setpoint with direct access to the control panel
field
Water setpoint from the parameter menu
field
Setpoint DHW
30 - 60°C
Heating setpoint home [P401]
30 - 60°C
DHW anti-legionella setpoint
50 - 60°C
Heating setpoint home [P401] + Offset heating night [P402]
50 - 60°C
Customized climatic curve
COOlING
If the cooling climate curve [P586] is configured to "0", the wa-
ter setpoint will be calculated based on the customized cooling
climate curve.
The customized cooling climate curve can be defined using the
following parameters:
Parameter
Description
Default
Min.
Max.
P587
OAT min customized
20°C
0°C
30°C
P588
OAT max customized
35°C
24°C
46°C
P589
Personalized minimum water temperature
10°C
5°C
18°C
P590
Customized maximum water temperature
18°C
5°C
18°C
Example:
CUStOMIZED COOlING ClIMAtIC CURVES
0
5
15
20
25
10
15
20
25
30
35
40
45
50
10
P590
P587
P588
P589
min
Default
max
OAT (°C)
WSP (°C
)
—
If the OAT is not valid, the water setpoint is equal to the
minimum personalized water temperature [P589].
—
If the OAT is above the maximum current OAT threshold, the
water setpoint is equal to the maximum personalized wa-
ter temperature [P590].
—
If the minimum OAT is greater than or equal to the maxi-
mum current OAT threshold, the water setpoint is equal to
the maximum customized water temperature [P590].
HEAtING
If the climatic curve heating [P581] configured on " 0 ", the water set point will be calculated based on the customized heating