![Riello 20161608 Скачать руководство пользователя страница 47](http://html1.mh-extra.com/html/riello/20161608/20161608_installation-and-technical-service-instructions_1460011047.webp)
47
INStAllAtION
Par.
Jbus
Sigla
Description
field
Default
Unit
Control panel
CCN
table
373
WATER_PUMP_
START_Nb
Number of starts of the water
pump
-
RO
RUNTIME1
374
0bDAH
WATER_PUMP_
RUNTIME
Hours of operation of the water
pump
h
RO
RO
RUNTIME1
379
UNIT_WEAR_FACTOR Wear factor
-
RUNTIME1
381
RUNTIME2_RESET Restoration of the operating time
made by the user
0°3
-
RW
RUNTIME2
382
COMP_RUNTIME
Hours of compressor operation
h
RO
RUNTIME2
383
bACKUP_RUNTIME Hours of emergency operation
h
RO
RUNTIME2
384
COOLING_RUNTIME Hours in cooling mode
h
RO
RUNTIME2
385
HEATING_RUNTIME Hours in heating mode
h
RO
RUNTIME2
386
DHW_RUNTIME
Hours in DHW mode
h
RO
RUNTIME2
387
DEFROST_RUNTIME Hours in antifreeze mode
h
RO
RUNTIME2
388
ENERGY_IN_
HEATING
Energy consumed in heating
kWh
RO
RUNTIME2
389
ENERGY_IN_
COOLING
Energy consumed in cooling
kWh
RO
RUNTIME2
391
CHIL_S_S
Start/stop unitร
0°1
-
392
HC_SEL
Heating / Cooling selection
0°1
-
393
EMSTOP
Invalid configuration
0°1
-
394
CAPACITY_REQUEST Required capacity
0°100
%
399
RESETDEV
Device reset
0°1
-
Setpoint parameters
Par.
Jbus
Sigla
Description
field
Default
Unit
Control panel
CCN
table
401
HEAT_OCC_WATER_
STP
Home heating setpoint (water)
20,0 - 60,0
45.0
1/10°C
RW
WAT_STP
402
HEAT_UNO_WATER_
OFFSE
Night heating offset (water)
=-10-0
0.0
1/10 K
RW
WAT_STP
403
HEAT_ECO_WATER_
OFFSE
Offset heating away (water)
=-10-0
-5.0
1/10 K
RW
WAT_STP
404
DHW_ECO_STP
DHW setpoint ECO
45.0
1/10°C
405
DHW_ANTI_
LEGIONELLA_
DHW anti-legionella setpoint
50,0 - 60,0
60.0
1/10°C
RW
WAT_STP
406
DHW_STP
Setpoint DHW
30,0 - 60,0
50.0
1/10°C
RW
WAT_STP
407
COOL_OCC_WATER_
STP
Home cooling setpoint (water)
5,0 - 18,0
12.0
1/10°C
RW
WAT_STP
408
COOL_UNO_WATER_
OFFSE
Night cooling offset (water)
0,0 - 10,0
0.0
1/10 K
RW
WAT_STP
409
COOL_ECO_WATER_
OFFSE
Offset cooling away (water)
0,0 - 10,0
5.0
1/10 K
RW
WAT_STP
410
HEAT_HYSTERESIS Heating hysteresis (water)
0,5 - 2,0
1.0
1/10 K
RW
WAT_STP
411
COOL_HYSTERESIS Cooling hysteresis (water)
0,5 - 2,0
2.0
1/10 K
RW
WAT_STP
412
HEAT_CURV_MAX_
STP_OF
Maximum heating curve setpoint
offset
=-5-5
0.0
1/10 K
RW
WAT_STP
413
COOL_CURV_MIN_
STP_OF
Minimum cooling curve setpoint
offset
=-5-5
0.0
1/10 K
RW
WAT_STP
421
HEAT_OCC_AIR_STP Home heating setpoint (air)
12,0 - 34,0
19.0
1/10°C
RW
AIR_STP
422
HEAT_UNO_AIR_
OFFSET
Night heating offset (air)
=-10-0
-2.0
1/10 K
RW
AIR_STP
423
HEAT_ECO_AIR_
OFFSET
Offset heating outside the home
(air)
=-10-0
-4.0
1/10 K
RW
AIR_STP
424
COOL_OCC_AIR_STP Home cooling setpoint (air)
20,0 - 38,0
26.0
1/10°C
RW
AIR_STP
425
COOL_UNO_AIR_
OFFSET
Night cooling offset (air)
0,0 - 10,0
2.0
1/10 K
RW
AIR_STP
426
COOL_ECO_AIR_
OFFSET
Offset cooling away from home
(air)
0,0 - 10,0
4.0
1/10 K
RW
AIR_STP
427
HOME_ANTI_
FREEZE_STP
Home antifreeze setpoint
6,0 - 12,0
6.0
1/10°C
RW
AIR_STP
428
AIR_DELTA_STP
Air delta setpoint
0,2 - 1,0
0.5
1/10 K
RW
AIR_STP
429
IAT_RESET_FACTOR IAT recovery factor
0,0 - 2,0
0.0
RW
AIR_STP