INStAllAtION
Parameters overview
This section includes an overview of all parameters that can be
read or modified by the user.
The parameters are sorted as follows:
—
001 - 299 Display parameters
—
301 - 399 Maintenance parameters
—
401 - 499 Setpoint parameters
—
501 - 799 Configuration parameters
legend:
No
No access
RO
Reading only
RW Reading/writing
RO/d
Reading and display on the control panel
RO/F
Parameter reading and forcing via CCN only
•
Proceed as follows to access the filters:
—
press any key to activate the control panel
—
hold down the keys simultaneously
and
for 2 sec-
onds
The display asks for the password for advanced settings.
Enter your password(
0120)
—
push
or
to select the first number
—
push
to confirm the selection and access the next item
—
keep the key pressed
for 2 seconds to validate the
password and log in
To select:
—
push
or
to select the desired parameter
To change:
—
keep the key pressed
for 2 seconds
—
push
or
to change the value
—
push
to confirm the selection and access the next item
—
keep the key pressed
for 2 seconds to store the pa-
rameter
Finish the settings:
—
keep the key pressed
for 2 seconds to exit
Dispalying parameters
Par.
Modbus
Sigla
Description
field
Default
Unit
Control panel
CCN
table
001
0bbAH
OAT
Outdoor Air Temperature
-40.0°115.6
RO
RO/No
Force
GENUNIT
002
IAT
Indoor Air Temperature
-40.0°115.6
GENUNIT
003
0bb8H
EWT
(Entering Water Temperature), inlet
water temperature
-40.0°115.6
1/10°C
RO
RO/No
Force
GENUNIT
004
0bb9H
LWT
(Leaving Water Temperature), outlet
water temperature
-40.0°115.6
1/10°C
RO
RO/No
Force
GENUNIT
005
189EH
REFR_T
Refrigerant Temperature
-40.0°115.6
1/10°C
RO
RO/No
Force
GENUNIT
006
SPARE_TEMP
Replacement temperature
-40.0°115.6
1/10°C
GENUNIT
007
ROOM_TEMP
Ambient temperature
-40.0°115.6
1/10°C
GENUNIT
008
SST
Saturated suction temp
1/10°C
GENUNIT
009
189DH
TS
Suction temperature
1/10°C
RO
RO/No
Force
GENUNIT
010
189CH
TD
Discharge temperature
1/10°C
RO
RO/No
Force
GENUNIT
011
189FH
TE
Air exchanger lower temperature
1/10°C
RO
RO/No
Force
GENUNIT
012
TL
Air exchanger upper temperature
1/10°C
GENUNIT
013
18A0H
TO
Inv. Outdoor air temperature
1/10°C
RO
RO/No
Force
GENUNIT
014
TH
Heat sink temperature
1/10°C
GENUNIT
015
SH
Superheating temperature
1/10 K
GENUNIT
016
SH_TARGET
Temp. target superheating
1/10 K
GENUNIT
017
INV_DC_VOLTAGE High voltage CC inverter
V
GENUNIT
018
HV_COMM_STATUS AT bus communication status
0/1
-
GENUNIT
019
INV_CURRENT_
MODE
Current inverter mode
0°22
-
GENUNIT
020
FREQ_MIN
Compressor min. frequency
1/10 Hz
GENUNIT