44
INStAllAtION
Par.
Modbus
Sigla
Description
field
Default
Unit
Control panel
CCN
table
104
SAFETY_SW
Safety switch status
0/1
-
INPUT
105
18A6H
FLOW_SW
Flow switch status
0/1
-
RO
RO/No
Force
INPUT OR
106
0710H
CUST_DI5_STATUS Custom DI#5 status
0/1
-
RO
RO/No
Force
DHW_STAT
107
0711H
CUST_DI6_STATUS Custom DI#6 status
0/1
-
RO
RO/No
Force
INPUT O
108
0712H
CUST_DI7_STATUS Custom DI#7 status
0/1
-
RO
RO/No
Force
DHW_STAT
109
0713H
CUST_DI8_STATUS Custom DI#8 status
0/1
-
RO
RO/No
Force
INPUT O
110
POWER_
LIMITATION_SW
Power limit switch
0/1
-
DHW_STAT
111
OFF_PEAK_SW
Shut-off switch during hours of
high energy cost
0/1
-
INPUT OR
112
LOADSHED_SW
Load removal request switch
0/1
-
DHW_STAT
113
SOLAR_SW
Solar input switch
0/1
-
INPUT
114
DHW_REQUEST_SW DHW request from the tank
0/1
-
DHW_STAT
115
DHW_PRIORITY_SW DHW priority switch
0/1
-
DHW_STAT
116
0720H
DHW_ANTI_LEG_SW DHW anti-legionella request
0/1
-
RW
RW/
Supervisor
DHW_STAT
117
SUMMER_SW
Summer switch
0/1
-
DHW_STAT
120
EXTERNAL_ALARM_
SW
External alarm switch
0/1
-
DHW_STAT
201
0730H
DHW_MODE
DHW mode
0°2
-
RO
RO/No
Force
DHW_STAT
202
DHW_OVERRIDE
Override DHW
-1°100
-
DHW_STAT
203
DHW_DEMAND
DHW request from the tank
0/1
-
DHW_STAT
204
DHW_CONDITIONS Conditions DHW
0/1
-
DHW_STAT
205
DHW_CONTROL_
POINT
DHW control point
30.0°60.0
1/10°C
DHW_STAT
206
0800H
DHW_TT
DHW tank temperature
-40.0°115.6
1/10°C
RO
RO/No
Force
DHW_STAT
207
SHC_TIMER
Current SHC runtime
min
DHW_STAT
208
DHW_TIMER
Current DHW runtime
min
MSL_STAT
209
DHW_EXCEPTION_
TIMER
DHW exception timer
0°1440
min
MSL_STAT
210
0503H
DHW_VLV
DHW diverter valve
0/1
-
RO
RO/No
Force
MSL_STAT
211
DHW_EHS
ACS electric heater stage
0/1
-
MSL_STAT
212
DHW_RUNNING
DHW operating status
0/1
-
MSL_STAT
221
CHWSTEMP
Cooler water circuit temp
-40.0°115.6
1/10°C
MSL_STAT
222
MSL_CAPACITY
Overall Master / Slave capacity
0°100
%
223
MST_REQUEST
Master capacity required
0°100
%
224
SLV1_REQUEST
Slave capacity request no.1
0°100
%
225
SLV2_REQUEST
Slave capacity request no.2
0°100
%
226
SLV3_REQUEST
Slave capacity request no.3
0°100
%
227
MSL_ICON_STATUS Master / slave status icons
0°3
-
228
MSL_ATIVE_FLAG
Master / slave activation flag
0/1
-
229
MSL_OVERALL_
STATUS
Master / slave status
-1°22
-
230
MAST_STATUS
Master status
-1°109
-
231
SLV1_STATUS
Stato Slave #1
-1°109
-
232
SLV2_STATUS
Stato Slave #2
-1°109
-
233
SLV3_STATUS
Stato Slave #3
-1°109
-
234
MSL_DEMAND_
LIMIT
Mast / Slv capacity limitation
0°100
100
%
235
MSL_ACTUAL_
PRIORITY
Mast/Slv Prioritร
0
-
239
MSL_CTRL_PNT2
2nd Control Point water
°C