fUNCtIONS
climate curve.
The customized heating climate curve can be defined using the
following parameters:
Parameter
Description
Default
Min.
Max.
P582
OAT min customized
-7°C
-30°C
10°C
P583
OAT max customized
20°C
10°C
30°C
P584
Personalized minimum water temperature
20°C
20°C
40°C
P585
Customized maximum water temperature
38°C
30°C
60°C
Example:
CUStOMIZED HEAtING ClIMAtIC CURVES
5
15
25
35
45
55
65
-40
-30
-20
-10
0
10
20
30
P585
P582
P583
P584
min
Default
max
OAT (°C)
WSP (°C
)
—
If the OAT is not valid, the water setpoint is equal to the
maximum personalized water temperature [P585].
—
If the OAT is above the maximum current OAT threshold, the
water setpoint is equal to the minimum personalized wa-
ter temperature [P584].
—
If the minimum OAT is greater than or equal to the current
maximum OAT threshold, the water setpoint is equal to the
customized minimum water temperature [P584].
Climatic curve offset (default and customized)
Two other parameters are configurable to adjust the water set-
point according to customer needs:
—
for the cooling curve, the minimum cooling water set-
point[P589] can be changed by an offset at the foot of the
curve (minimum cooling curve setpoint offset[P413])
—
and for the heating curve, the maximum heating water
setpoint [P585] can be changed by an offset at the foot of
the curve (maximum heating curve setpoint offset [P412])
Example:
COOlING ClIMAtIC CURVES WItH OffSEt ON tHE lOWER SIDE
0
5
10
15
20
25
10
15
20
25
30
35
40
45
50
P413
OAT (°C)
WSP (°C
)