fUNCtIONS
Climatic curve
OAt min.
OAt max.
temp. water min.
temp. water max.
K12
3,5°C
20°C
27°C
60°C
HEAtING ClIMAtIC CURVES (K7 AND K8)
15
25
35
45
55
65
-30
-20
-10
0
10
20
30
K7
K8
OAT (°C)
Setpoint dell'acqua (°
C)
—
If the OAT is valid (not transmitted by the inverter, value out
of range, etc.), the water setpoint is equal to the maximum
current water temperature.
—
If the OAT is above the maximum current OAT threshold,
the water setpoint is equal to the minimum current water
temperature.
The climatic curve corresponds to the water setpoint for the
Home mode. To define the other occupation modes, it is nec-
essary to configure the Night heating offset [P402] and the Away
heating offset[P403]:
HEAtING ClIMAtIC CURVES RElAtED tO WORKING MODE HOME
5
15
25
35
45
55
65
-40
-30
-20
-10
0
10
20
30
Home
Sleep
Away
P403
P402
WSP (°
C)
OAT (°C)
fixed water setpoint
If the cooling climate curve [P586] or the heating climate curve
[P581] are configured to "-1", the water control point will be de-
termined based on the occupation mode, with direct access to
the control panel.
The water setpoint with direct access to the control panel (refer
to the user manual of the control panel)
COOlING
Control panel
occupation
Water setpoint with direct access to the control panel
field
Water setpoint from the parameter menu
field
Cooling setpoint home
5 - 18°C
Cooling setpoint home [P407]
5 - 18°C
Cooling setpoint night
5 - 18°C
Cooling setpoint home [P407] + night cooling offset [P408]
0 - 10°C