![Riello 20161608 Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/riello/20161608/20161608_installation-and-technical-service-instructions_1460011046.webp)
46
INStAllAtION
Par.
Jbus
Sigla
Description
field
Default
Unit
Control panel
CCN
table
323
RAT_MOD
QT: Evaluation mode
0°4
-
RW/F
QCH_TEST
0 = Evaluation off
1 = Cooling evaluation
2 = Heating rating
3 = Cooling ramp
4 = Heating ramp
324
RAT_FRQ
QT: Evaluation frequency
-120°120
1/10 Hz
RW/F
QCH_TEST
325
FAN_LOW
QT: Lower fan speed
0°999
rpm
RW/F
QCH_TEST
326
FAN_UPP
QT: Higher fan speed
0°999
rpm
RW/F
QCH_TEST
327
PMV_POS
QT: PMV position
0°999
-
RW/F
QCH_TEST
328
CMP_HTR
QT: compressor heater
0°1
-
329
2WAYVLV
QT: equalization valve
0°1
-
330
4WAYVLV
QT: reverse cycle valve
0°1
-
331
18CEH
PMP
QT: Water pump speed
0°100
%
RW
RW/F
QCH_TEST
332
EXH_HTR
QT: bPHE heater
0°1
RW/F
QCH_TEST
on/off
333 0701H
ADD_PMP
QT: Additional pump
0°1
RW
RW/F
QCH_TEST
on/off
334 0702H
SPR_REL
QT: Relรร (K5)
0°1
RW
RW/F
QCH_TEST
on/off
335
DHW_VLV
QT: Diverter valve DHW
0°1
RW/F
QCH_TEST
on/off
336
bOILER
QT: boiler or EHS1
0°1
RW/F
QCH_TEST
on/off
320
0703H
CUSTDO5
QT: DO n.5 customized
0°1
-
RW
on/off
337
0704H
CUSTDO8
QT: DO n.8 customized
0°1
-
RW
RW/F
QCH_TEST
on/off
338
0705H
CUSTDO9
QT: DO n.9 customized
0°1
-
RW
RW/F
QCH_TEST
on/off
339
HP_MAX
Maximum high pressure
KPa
340
ALMRESET
Alarm reset
0°1
-
RO
QCH_TEST
No/sรร
341
ALM
Alarm status
0°1
-
RW/F
ALARM
Normal/Alarm
342
ALERT
Alert status
0°1
-
RO
ALARM
No/sรร
343
SHUTDOWN
State of arrest
0°1
-
RO
ALARM
No/sรร
344
INV_ERROR_CODE Inverter error (code)
0°255
RO
ALARM
345
INV_ERROR_ALPHA Inverter error (Alpha)
0°65535
-
RO
ALARM
346
18A7H
ALM_CODE_bITMAP1 Drive error code 1
0°65535
-
RO
RO
ALARM
347
18A8H
ALM_CODE_
bITMAP2
Drive error code 2
0°65535
-
RO
RO
ALARM
348
18A9H
ALM_CODE_
bITMAP3
Drive error code 3
0°65535
-
RO
RO
ALARM
349
18AAH
ALM_CODE_
bITMAP4
Drive error code 4
0°65535
-
RO
RO
ALARM
350
ALM_01
Current alarm n.1
0°200
-
RO
ALARM
351
ALM_02
Current alarm n.2
0°200
-
RO
ALARM
352
ALM_03
Current alarm n.3
0°200
-
RO
ALARM
353
ALM_04
Current alarm n.4
0°200
-
RO
ALARM
354
ALM_05
Current alarm n.5
0°200
-
RO
ALARM
360
ALM_01P
Previous alarm n.1
0°200
-
RO
ALARM
361
ALM_02P
Previous alarm n.2
0°200
-
RO
ALARM
362
ALM_03P
Previous alarm n.3
0°200
-
RO
ALARM
363
ALM_04P
Previous alarm n.4
0°200
-
RO
ALARM
364
ALM_05P
Previous alarm n.5
0°200
-
RO
ALARM
370
RUNTIME1_KEY
Maintenance runtime key
-
RUNTIME1
371
COMP1_START_Nb Number of starts of the compressor
-
RO
RUNTIME1
372
18A4H
COMP1_RUNTIME Hours of compressor operation
h
RO
RO
RUNTIME1
Содержание 20161608
Страница 1: ...NXH 005 015 cod Doc 0096185 rev 0 05 2020 EN INSTALLATION AND TECHNICAL SERVICE INSTRUCTIONS ...
Страница 65: ......
Страница 66: ......
Страница 67: ......