MAINtENANCE
—
the connections on the water side are clean and do not
show signs of leaks.
4.6 Maintenance
9
before any intervention on the unit, make sure that the cir-
cuit is isolated and that there is no voltage. Note that it may
take 5 minutes for the circuit capacitors to fully discharge
after isolating the circuit. Only qualified personnel are au-
thorized to work on the VFD.
In case of alarm or persistent problem related to the VFD, contact
the assistance service.
VFDs equipped with units do not require an insulation test, even
if they are replaced; they are in fact checked systematically be-
fore delivery. In addition, the filter components installed in the
VFD can distort the measurement and can also be damaged. If
there is a need to check the insulation of the components of the
appliance (fan motors and pumps, cables, etc.), the VFD must be
disconnected from the power circuit.
4.7 Refrigerant volume
The unit must be started in cooling mode to find out if the unit
load is correct by checking the actual subcooling.
A small loss of refrigerant compared to the initial load will be
evident in the cooling mode and will affect the subcooling value
obtained at the outlet of the air heat exchanger (condenser), but
will not be visible in heating mode.
9
It is therefore not possible to optimize the refrigerant charge
in the heating mode after a leak. The unit will need to be
started in cooling mode to check if an additional load is re-
quired.