48
INStAllAtION
Configuration parameters
Par.
Jbus
Mnemonic
Description
field
Default
Unit
Control panel
CCN
table
500
01F4H
CUST_DO5_TYPE Config DO#5 customized
0°13
0 = Disabilitato
1 = Unit in alarm (ancora funzionante)
2 = Unit in alarm (not running)
3 = Unit in Standby (request satisfied)
4 = Unit running (Cool, Heat, DHW, defrost)
5 = Unit running in cooling
6 = Unit running in heating
7 = Unit running DHW
8 = Unit in defrost
9 = IAT reached (FCU)
10 = Electric heater #2 (EH2)
11 = Electric heater #3 (EH3)
12 = Pool diverter valve
13 = User controlled output (via Jbus/Modbus)
4
-
RW
RW/No
Force
GEN_CONF
501
SAFETY_SW_TYPE Type of safety switch
1°3
1 = Off contact: unit stopped with open contact
2 = Safety switch for underfloor heating system:
heating not allowed if the contact is open
3 = Safety switch for underfloor cooling: cooling
not allowed if the contact is open
1
-
RW
GEN_CONF
502
CUST_DI5_TYPE Config DI#5 customized
-15°15
0 = Disabilitato
1 or -1 = Capacity limitation switch
2 or -2 = High consumption band operation
switch
3 or -3 = Loadshed Request Switch
4 or -4 = Solar input switch
5 or -5 = DHW request from the DHW tank
6 or -6 = Priority button ACS
7 or -7 = Anti-Legionella cycle request button
8 or -8 = Summer switch
9 or -9 = Pool priority button
10 or -10 = Contact on swimming pool pump
11 or -11 = Energy Meter Input (1 kWh/pulse)
12 or -12 = Energy Meter Input (0.5 kWh/pulse)
13 or -13 = Energy Meter Input (0.2 kWh/pulse)
14 or -14 = Energy Meter Input (0.1 kWh/pulse)
15 or -15 = External alarm
1
-
RW
GEN_CONF
503
CUST_DI6_TYPE Config DI#6 customized
0
-
RW
GEN_CONF
504
CUST_DI7_TYPE Config DI#7 customized
0
-
RW
GEN_CONF
505
CUST_DI8_TYPE Config DI#8 customized
0
-
RW
GEN_CONF
506
01FAH
CUST_DO8_TYPE Config DO#8 customized
1
-
RW
RW/No
Force
GEN_CONF
507
01FbH
CUST_DO9_TYPE Config DO#9 customized
2
-
RW
RW/No
Force
GEN_CONF
508
TR_TYPE
Type of coolant
temperature
0°2
0 = Mounted on the plate exchanger
1 = Mounted after the PMV less than 10m
2 = Mounted after the PMV at more than 10m
0
-
RW
GEN_CONF
509
EWT_TYPE
Type of sensor EWT
0/1
0 = No sensor EWT
1 = Sensor EWT present
1
-
RW
GEN_CONF
510
IAT_TYPE
Type of sensor IAT
0°3
0 = No sensor IAT
1 = 10 KOhms Thermistor (accessory)
2 = 5 KOhms Thermistor
3 = 3 KOhms Thermistor
0
-
\
GEN_CONF
511
1933H
OAT_TYPE
Type of sensor OAT
0°3
0 = No OAT additional
1 = 10 KOhms Thermistor
2 = 5 KOhms Thermistor
3 = 3 KOhms Thermistor (accessorio)
0
-
RW
RW/No
Force
GEN_CONF
512
IAT_bIAS
Type of sensor IAT
-5.0°5.0
0.0
1/10 K
RW
GEN_CONF
513
OAT_bIAS
bias sensor OAT
-5.0°5.0
0.0
1/10 K
RW
GEN_CONF
514
0894H
OAT_MIN_
HEATING
OAT minimum for heating
-20.0°10.0
-20.0
1/10°C
RW
RW/No
Force
GEN_CONF
515
OAT_MAX_
HEATING
OAT maximum for heating
5.0°99.0
99.0
1/10°C
RW
GEN_CONF
516
OAT_MIN_
COOLING
OAT minimum for cooling
-10.0°40.0
0.0
1/10°C
RW
GEN_CONF
517
086DH
ANTI_FREEZE_
DELTA_ST
Heat exchanger antifreeze
setpoint
0.0°6.0
0.0
1/10 K
RW
RW/No
Force
GEN_CONF
518
NIGHT_MODE_
START
Night mode start time
00:00°23:59
00:00
hh:mm
RW
GEN_CONF