SCC - Sequence of events
Low temperature steam: Temperature range 30-97°C
(85-207°F)
Function step
Responsible sensor
1
Select Wet heat (Temp 30-97°C (85-207°F))
2
Select time or core temperature
3
Close cabinet door
Reed switch S3
4
Check water level inside steam generator
Level electrode S2 inside Steam Gen
5
Time based preheating of steam generator,
if B5 is below 85°C (185°F)
Thermocouple B5 inside Steam Gen.
6
Timer starts after successful preheating
Logic on PCB
7
Steam supply until set temperature inside cabinet
is reached
Cabinet sensor B1
8
Adding of Hot Air from 93°C (200°F) possible
(only 50%)
Cabinet sensor B1
9
Quenching (set to 70°C/158°F)
Thermocouple B2
Note: Steam heating only active when humidity ap (S4) is in closed position!
Below 98°C fan at lowest speed when no energy required for longer than 2 minutes.
Additional functions possible: 4 Fan speeds (Standard = Level 3), pulsed fan wheel, ½ Energy,
HACCP output, T.
B1
B6 - B11
F4
P1
M3
S4
M4
M6
Y1
Y2
Y3
B2
M1
S2
M7
S12
B4
B5
F3
S3
Y4
S11
M12
Care
Содержание Combi Master
Страница 1: ...Edition 10 2008a 1 Training Manual SCC Line SelfCooking Center Combi Master...
Страница 2: ...2 Edition 10 2008a...
Страница 34: ...34 CM Edition 10 2008...
Страница 35: ...35 SCC Edition 10 2008a SCC Control panel...
Страница 47: ...47 SCC Edition 10 2008a Parts identi cation CareControl 1 2 3 3 4 4 11 1 2 3 4 11 4 2 3 1 2 11...
Страница 58: ...58 SCC Edition 10 2008a...
Страница 66: ...66 SCC Edition 10 2008a...
Страница 100: ...100 SCC Edition 10 2008a...
Страница 126: ...126 Gas Edition 10 2008a...
Страница 139: ...Edition 10 2008a 139 UltraVent...
Страница 153: ...153 Common Information Edition 10 2008a...
Страница 166: ...166 Trouble shooting SCC Edition 10 2008a...
Страница 177: ...177 SCC Edition 10 2008a...
Страница 195: ...195 Common Information Edition 10 2008a...