SECTION 19: T
ROUBLESHOOTING
131 of 143
Burner (continued)
19.4 Gas Operation
PROBLEM
POSSIBLE CAUSE
SOLUTION
Occasional Locko
u
ts for No
Apparent Reason
Occasional lo
w
v
oltage s
u
pply. Ha
v
e local
u
tility correct.
Occasional lo
w
gas s
u
pply press
u
re.
Ha
v
e local
u
tility correct.
Air leak in oil s
u
ction line or check
v
al
v
e not
holding.
Correct as req
u
ired.
PROBLEM
POSSIBLE CAUSE
SOLUTION
B
u
rner Motor R
u
ns,
bu
t
Pilot Does Not Light
Gas s
u
pply to
bu
rner sh
u
t off.
Make s
u
re all man
u
al gas s
u
pply
v
al
v
es
are open. A
u
tomatic high press
u
re.
Pilot solenoid
v
al
v
e not opening.
Listen and feel for
v
al
v
e act
u
ation. Sole-
noid
v
al
v
e not
b
eing po
w
ered--check elec-
trical circ
u
itry. Replace coil or entire
v
al
v
e
if coil is
bu
rned o
u
t.
Defecti
v
e gas pilot reg
u
lator.
Replace.
Gas press
u
re too high or too lo
w
at pilot orifice. Refer to gas pilot adj
u
stments for correct
settings. Readj
u
st as req
u
ired.
Defecti
v
e ignition transformer.
Replace.
Incorrect ignition electrode settings.
Refer to gas pilot adj
u
stments for correct
settings.
Defecti
v
e flame safeg
u
ard control or pl
u
g in
p
u
rge timing card.
Replace as req
u
ired.
Air flo
w
s
w
itch not making circ
u
it.
Check o
u
t electrically and correct pres-
s
u
re adj
u
stment on s
w
itch If req
u
ired.
Defecti
v
e air flo
w
s
w
itch.
Replace.
Air s
w
itch negati
v
e press
u
re sensing t
ub
e o
u
t
of position.
Reposition as necessary.
B
u
rner Motor R
u
ns and
Pilot Lights,
bu
t Main Gas
Flame is Not Esta
b
lished.
Main sh
u
t off or test cock closed.
Check to make certain f
u
lly open.
Pilot flame signal reading too lo
w
to p
u
ll in
flame safeg
u
ard relay.
Refer to gas pilot settings section and
readj
u
st as req
u
ired.
Defecti
v
e a
u
tomatic main or a
u
xiliary gas sh
u
t
off
v
al
v
es.
Check electrical circ
u
itry to
v
al
v
es.
Replace
v
al
v
es or correct circ
u
itry as
req
u
ired.
Defecti
v
e flame safeg
u
ard control or pl
u
g in
amplifier.
Check and replace as req
u
ired.
B
u
tterfly
v
al
v
e set incorrectly on mod
u
lating
bu
rner.
Readj
u
st as req
u
ired.
Main gas press
u
re reg
u
lator atmospheric
v
ent
line o
b
str
u
cted.
Correct.
Defecti
v
e main gas press
u
re reg
u
lator
Replace.
Misadj
u
sted main gas press
u
re reg
u
lator
Readj
u
st to meet req
u
ired operational
v
al-
u
es.
Содержание 7500 136
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 10: ......
Страница 12: ......
Страница 33: ...SECTION 6 LIFTING AN AIR TURNOVER UNIT 21 of 143 FIGURE 10 Lifting an Air Turnover Unit Base Section...
Страница 36: ...7500 SERIES INSTALLATION OPERATION AND SERVICE MANUAL 24 of 143 FIGURE 12 Air Turnover Unit Sections Schematic...
Страница 67: ...SECTION14 ELECTRICAL 55 of 143 FIGURE 38 Wiring Diagram Key...
Страница 115: ...SECTION 15 SEQUENCE OF OPERATION 103 of 143 FIGURE 83 Wiring Subbase and Sequence Chart for RM7897 Burner Control Module...
Страница 156: ......