Connecting DC power
Connect the power wires from the R220RCPSU-DC to the DC source as follows:
•
Red wire to DC source 0
•
Black wire to DC source -48V
•
Green wire to DC source ground
WARNING!
Ensure power to the power feed cables is OFF before routing and connecting the
cables.
WARNING!
To reduce the risk of electrical shock or energy hazards, comply with these
precautions:
•
Make sure you have an adequate number of properly grounded electrical outlets for your
system and any other peripheral devices.
•
The unit shall be supplied by a reliably grounded SELV power supply or centralized DC source,
and shall be reliably grounded to protective earth.
•
The unit shall be installed in a restricted access area in accordance with the authority having
jurisdiction.
Power consumption
The R220 supports many configurations for I/O, storage, and computation.
documents
the power consumption of a maximum configuration where PCIe extenders are used for the
front I/O modules, and each front I/O module can consume up to 35 watts. The table
represents the maximum power consumption for each component, not the actual supported
maximum power consumption.
Table 4. R220 component power consumption
Component
Quantity
Unit power (watts)
Total power (watts)
Motherboard
1
88
88
CPU
2
105
210
75W PCIe card
2
75
150
Front I/O module
4
35
140
2.5" SAS HDD
5
10
50
Blower
4
48
192
Содержание R220
Страница 1: ...R220 NETWORK APPLIANCE July 2014 Setup Guide ...
Страница 32: ...3 Installing optional components 32 Figure 18 Installing removing the I O module ...
Страница 34: ...3 Installing optional components 34 Figure 20 Inserting the drive carrier into the drive cage ...
Страница 42: ...3 Installing optional components 42 Figure 27 Installing the rail kits into a threaded hole EIA 4 post rack ...
Страница 45: ...3 Installing optional components 45 Figure 29 Installing the rail kits into a Telecom 2 post rack ...