3 – Event Messages
Alarm Events
3-24
59060-04 A
S
(A1005.004A) (Temporary license for Fabric Security will expire in hours hour(s))
Meaning:
The temporary Fabric Security license will expire in the time
displayed.
Action:
Purchase and install the Fabric Security License to continue using
the security feature.
(A1005.004B) (The switch was reset due to firmware upgrade issues)
Meaning:
After a firmware upgrade, the Serial Prom Cyclic Redundancy
Check (CRC) did not match what was expected. It is likely that
licenses were updated on the switch while running older firmware.
Action:
Check your license configuration for changes.
(A1005.004C) (ICCnumber cable installed - ALARM CLEARED)
Meaning:
A HyperStack cable has been connected to the specified
Inter-Chassis Connection (ICC) port and the associated alarm has
been cleared.
Action:
None.
(A1005.004D) (ICCnumber cable not installed - ALARM SET)
Meaning:
A HyperStack cable is not connected to the specified Inter-Chassis
Connection (ICC) port and the associated alarm has been set.
Action:
None.
(A1005.004E) (Attempts to login backend switch fail because backend switch does not
support NPIV.)
Meaning:
The backend fabric switch does not support N_Port ID
Virtualization (NPIV) which in turn brings down the TF_Port.
Action:
Ensure that the backend fabric switch supports NPIV.
(A1005.004F) (Media device sensor is value units. Transitioning from state to state)
Meaning:
The specified sensor (temperature, voltage, TxBias, TxPower,
RxPower) has set a fault. The sensor reports its value (°Celsius,
volts, milliAmps, milliWatts) and transition states (low alarm, low
warning, normal, high warning, high alarm).
Action:
For the temperature sensor transitioning from
low alarm
to
high
alarm
, cool the system. For all other sensors transitioning from
low
alarm
to
high alarm
, replace the media.