SECTION 4 – SYSTEM INSTALLATION
UL EX3830 ULC EX3830
2014-NOV-10 REV. 06 PagE 4-25
KITCHEN KNIGHT II Restaurant Fire Suppression Manual
Connecting the Flexible Conduit to the PYRO-CHEM
Control Head, Electrical Box, Pull Station, or Mechanical
Gas Valve (Continued)
5. Tighten the nut to the connector body, locking the flexible
conduit insert in place. See Figure 4-43.
TIgHTEN
CONNECTOR
NUT TO LOCK
IN FLEXIBLE
CONDUIT
INSERT
FIGURE 4-43
008072
6. Loosen the nut on the strain relief and thread the wire rope
through the strain relief. See Figure 4-44.
LOOSEN
NUT
FIGURE 4-44
008073
7. Tighten the body of the strain relief to the conduit connector.
See Figure 4-45.
TIgHTEN
STRaIN RELIEF
INTO CONDUIT
CONNECTOR
FIGURE 4-45
008074
8. Thread the wire rope through the flexible conduit. See
Figure 4-46. (If a splice is required in the flexible conduit,
proceed to “Splicing Installation Instructions.”)
FIGURE 4-46
008075
9. Slide the flexible conduit into the strain relief until it is
approximately 1/16 in. (1.6 mm) from the bottom of the flex-
ible conduit insert. See Figure 4-47.
STOP FLEXIBLE
CONDUIT
aPPROXIMaTELY
1/16 IN. (1.6 mm)
FROM THE BOTTOM
OF INTERNaL
FLEXIBLE CONDUIT
INSERT
FIGURE 4-47
008076
10. Tighten the strain relief nut onto the strain relief. See Figure
4-48.
TIgHTEN NUT
ON STRaIN
RELIEF
FIGURE 4-48
008077