![Pyro-Chem Kitchen Knight II Скачать руководство пользователя страница 83](http://html1.mh-extra.com/html/pyro-chem/kitchen-knight-ii/kitchen-knight-ii_technical-manual_1632695083.webp)
SECTION 5 – SySTEm maINTENaNCE
UL EX3830 ULC EX3830
2014-NOV-10 REV. 06 PagE 5-1
KITCHEN KNIGHT II Restaurant Fire Suppression Manual
GENERaL
The maintenance information listed in this section deals with the
limitations and parameters of this pre-engineered system. Those
individuals responsible for the maintenance of the KITCHEN
KNIgHT II system must be trained and hold a current PYRO-
CHEM certificate in a KITCHEN KNIgHT II training program.
SEmI-aNNUaL maINTENaNCE
1. Check that the hazard area has not changed.
2. Check that the system has not been tampered with, i.e.,
nozzles removed, nozzles not aimed properly, piping not
supported properly, blow off caps in place.
3. Check the entire system for mechanical damage.
4. Check all nozzle orifices to make certain they are not
plugged. apply a small amount of Dow Corning No. III sili-
cone grease across the opening of the nozzle tip. Replace
blow off caps or o-ring if necessary.
Note:
Rubber blow-off caps that have been installed in the
system for one year or more must be replaced.
5. Check the solenoid monitor.
CaUTION
Before continuing, remove the cover from the control
head and insert the safety pin in the hole in the slide
plate above the latching arm. This will secure the system,
preventing accidental discharge.
If the control head cover requires replacement, it must
only be replaced with the NMCH cover plate which does
not have a handle on the control head cover for local
actuation.
6. Disconnect the control head or pneumatic tubing from the
valve cap assembly of each agent cylinder. Remove the
carbon dioxide pilot cartridge in the control head. Remove
the safety pin from the slide plate. actuate the control head
to ensure it is functioning properly. Make certain the gas
shut-off valve and remote pull station are functioning prop-
erly.
Test the functionality of the control head with the cover in
place to verify there is no binding. If binding occurs, turn
the indicator mounting bolt until there is 1/16 (1.6 mm) clear-
ance between the front edge of the control head back box
and white indicator surface.
7. Inspect the pulley elbows for excessive grease buildup.
Clean elbows if necessary. Replace fusible links. (They
must be replaced semi-annually per NFPa 96.) Visually
inspect thermal detectors.
Note:
Refer to Section 4 – System Installation for control
head assembly resetting procedures.
NOTICE
Methods and frequency of inspection,
testing and maintenance of detectors
should be in accordance with NFPa-72.
8. Reinstall the carbon dioxide pilot cartridge, reconnect the
control head, and replace the control head cover and nylon
tie. See detailed cartridge installation instructions listed on
Page 4-20 (System Installation).
CaUTION
Before screwing the carbon dioxide pilot cartridge into the
actuator, ensure that the actuator has an o-ring installed.
If actuator is utilizing a Teflon washer, replace with o-ring
(Part No. 55531).
9. Inspect the cylinder pressure. Tap the gauge lightly to
ensure the needle is moving freely. If the gauge shows a
loss in pressure indicated by the needle being below the
green band, the tank should be removed and recharged per
the SYSTEM RECHaRgE section of Chapter VI (System
Recharge) in this manual.
aNNUaL maINTENaNCE
1. Inspect as per semi-annual maintenance instructions. Do
not reconnect control head at this time.
2. Disconnect the discharge piping from the valve outlet. Using
air or nitrogen, blow out the piping. Replace all nozzle caps.
3. Fixed temperature sensing elements of the fusible alloy
type must be replaced, at a maximum semi-annually, or
more frequently if necessary, to assure proper operation of
the system.
4. Test thermal detectors and remote pull stations per SYSTEM
CHECKOUT aFTER INSTaLLaTION section located in
Chapter IV (System Installation) of this manual. Per NFPa
72, two or more detectors per circuit should be tested. Note
individual detector location and date of testing. Within five
years, all detectors in system must be tested.
5. Replace the carbon dioxide pilot cartridge and o-ring (Part
No. 55531).
6. Record the date of installation on the cartridge with a felt-
tipped marker.
7. See detailed cartridge installation instructions listed on
Page 4-20 (System Installation).
CaUTION
Before screwing the carbon dioxide pilot cartridge into the
actuator, ensure that the actuator has an o-ring installed.
8. Reconnect the control head. Replace the control head
cover and nylon tie.