SECTION 3 – SYSTEM DESIGN
UL EX3830 ULC EX3830
2014-NOV-10 REV. 06 PagE 3-11
KITCHEN KNIGHT II Restaurant Fire Suppression Manual
NOZZLE COVERAGE AND PLACEMENT (Continued)
Appliance Protection (Continued)
8. Radiant/Electric Char-Broiler
(624 in.2 (40257 mm2) x 26
in. (660 mm) longest side maximum)
Note:
Radiant charbroilers are distinguished by the use of
heated metal strips (radiants) that are used for cooking.
Two nozzles are available for radiant char-broiler protection.
High proximity and low proximity.
The 1H nozzle (Part No. 551029) is used for high proximity
radiant char-broiler protection. This nozzle is a one flow
nozzle. The nozzle must be located
anywhere within the
perimeter
of the hazard area, 24 in. to 48 in. (609.6 mm to
1219 mm) above the cooking surface of the appliance and
aimed at the center of the broiler surface. See Figure 3-19.
The 1L nozzle (Part No. 551026) is used for low proximity
radiant char-broiler protection. This nozzle is a one flow
nozzle. The nozzle must be located
anywhere on the
perimeter
of the hazard surface, 13 in. to 24 in. (331 to
609.6 mm) above the cooking surface of the appliance and
aimed at the center of the broiler surface. See Figure 3-19.
006187PC
48 IN.
(1219 mm)
RADIANT
BROILER
1H NOzzLE LOCaTED
ANYwHERE
wITHIN THE PERIMETER
FOR HIgH PROXIMITY PROTECTION
1L NOzzLE LOCaTED
ANYwHERE
ON THE PERIMETER
FOR LOW
PROXIMITY
PROTECTION
1H
1L
1H, 1L
EDgE OF
HazaRD aREa
13 IN.
(331 mm)
24 IN.
(609.6 mm)
FIGuRE 3-19
9. Radiant/Electric Char-Broiler
(864 in.
2
(55741 mm
2
) x
36 in. (914 mm) longest side maximum)
Two nozzles are available for radiant char-broiler protection:
High proximity and low proximity.
The 2H nozzle (Part No. 551028) is used for high proximity
radiant char-broiler protection. This nozzle is a two flow
nozzle. The nozzle must be located
above any corner
of
the hazard surface, 36 in. to 48 in. (915 mm to 1219 mm)
above the cooking surface of the appliance and aimed at the
center of the broiler surface. See Figure 3-20.
006185PC
48 IN.
(1219 mm)
36 IN.
(915 mm)
HIGH PROXIMITY
RADIANT BROILER
NOzzLE (aNY
CORNER)
2H
2H
EDgE OF
HazaRD aREa
FIGuRE 3-20
The 2L nozzle (Part No. 551027) is used for low proximity
radiant char-broiler protection. This nozzle is a two flow
nozzle. The nozzle must be located
anywhere on the
perimeter
of the hazard surface, 13 in. to 36 in. (331 mm
to 914 mm) above the cooking surface of the appliance and
aimed at the center of the broiler surface. See Figure 3-21.
006186PC
36 IN.
(914 mm)
13 IN.
(331 mm)
LOw PROXIMITY
RADIANT BROILER
NOzzLE LOCaTED aNYWHERE aLONg
PERIMETER
OF HazaRD
aREa
2L
2L
EDgE OF
HazaRD aREa
FIGuRE 3-21
10. Lava Rock Char-Broiler
(624 in.
2
(40257 mm
2
) x 26 in.
(660 mm) longest side maximum)
Note:
Synthetic rock charbroilers are distinguished by the
use of lava, pumice, or synthetic rocks that are used for
cooking.
One nozzle is available for lava rock char-broiler protection:
High proximity and low proximity.
The 2L Nozzle (Part No. 551027) is used for high proximity
lava rock char-broiler protection. This nozzle is a two flow
nozzle. The nozzle must be located
anywhere within the
perimeter
of the hazard area, 24 in. to 35 in. (609.6 mm to
889 mm) above the cooking surface of the appliance and
aimed at the center of the broiler surface. See Figure 3-22.
The 2L nozzle (Part No. 551027) is used for low proximity
lava rock char-broiler protection. This nozzle is a two flow
nozzle. The nozzle must be located
anywhere on the
perimeter
of the hazard surface, 15 in. to 24 in. (381 mm to
609.6 mm) above the cooking surface of the appliance and
aimed at the center of the broiler surface. See Figure 3-22.
006187PC
35 IN.
(889 mm)
15 IN.
(381 mm)
24 IN.
(609.6
mm)
LAVA ROCk
CHAR-BROILER
2L NOzzLE LOCaTED
ANYwHERE
wITHIN THE PERIMETER
FOR HIgH PROXIMITY PROTECTION
2L NOzzLE LOCaTED
ANYwHERE
ON THE PERIMETER
FOR LOW
PROXIMITY
PROTECTION
2L
2L
2L
EDgE OF
HazaRD aREa
FIGuRE 3-22