SECTION 4 – SYSTEM INSTALLATION
UL EX3830 ULC EX3830
2014-NOV-10 REV. 06 PagE 4-19
KITCHEN KNIGHT II Restaurant Fire Suppression Manual
SYSTEM CHECkOUT AFTER INSTALLATION (Continued)
Completing System Checkout
1. Make certain the aUTOPULSE control panel is reset and
the control head is re-cocked and set. If the Model SM-120
Solenoid Monitor is used instead of an aUTOPULSE control
panel, energize the actuation/detection circuit by depress-
ing the push button on the solenoid monitor.
2. Using a felt-tipped marker, write the date of installation on
the CO2 pilot cartridge. Ensure that the actuator has an
o-ring installed, and screw the cartridge into the control
head actuator until hand tight. Continue installation of
cartridge by turning an additional 1/4 turn using a wrench or
pliers.
Use caution not to damage cartridge.
Note 1:
Four to five threads should be showing when the
cartridge in engaged properly. It is important that no more
than five threads be showing.
Note 2:
The cartridge and o-ring shall be replaced annually.
CAUTION
Do not over-tighten cartridge. Over-tightening can result in
premature puncturing of the cartridge seal.
3. Remove the pull pin from the hole in the slide plate and
install the control head cover. Insert the pull pin through the
local manual control handle and into the bushing. Secure
the pull pin with the tie provided.
NOTICE
Refer to NFPa-17a for additional inspec-
tion requirements.
ENCLOSURE INSTALLATION INSTRUCTIONS –
MODEL EN-MCU3 AND MODEL EN-S
Enclosure Mounting
The Model EN-MCU3 and/or EN-S Enclosure must be securely
anchored to the wall using bolts or lag screws. The wall to which
the enclosure is attached must be sufficiently strong. The enclo-
sure should never be fastened to drywall or similar material. If
this type of wall is encountered, studs must be located and the
enclosure fastened to them.
Three center mounting holes allow either enclosure to be
mounted on a single stud. Four corner mounting holes are also
available. See Figure 4-32.
FIGURE 4-32
002946PC