61
Transmitter
Select the type of transmitter connected (2-wire loop powered, 2-wire self-pow-
ered, 3-wire, or 4-wire).
Flow Units
Select the units of measure for the water volume, between gallons, liters, cubic
meters and million of gallons (MG).
Rate Units
Select the units of measure for the flow rate time base.
Flowmeter Max
Enter the flow rate at which the meter outputs a 20 mA signal.
Input Filter
Enter the mA below which the flow rate will considered 0. Typically any meter output
below 4.02 mA is actually 0 flow.
Name
The name used to identify the sensor may be changed.
Type
Select the type of sensor to be connected.
5.2.13 Analog Tank Level Input
Settings
Touch the
Edit
icon to view or change the settings related to the sensor.
Alarms
Low-Low, Low, High and High-High Alarms limits may be set.
Deadband
This is the Alarm Deadband. For example, if the High Alarm is 7.00, and the
deadband is 0.1, the alarm will activate at 7.01 and deactivate at 6.90.
Reset Calibration Values
Enter this menu to reset the sensor calibration back to factory defaults.
Alarm & Datalog
Suppression
If any of the relays or digital inputs are selected, any alarms related to this input
will be suppressed if the selected relay or digital input is active. At the same time,
all datalogs and graphs containing the input will show no data for the duration of
the activation.
Units
Enter the units of measure for the transmitter.
Tank Capacity
Enter the capacity of the tank when full in the units of measure entered above.
Empty At
Enter the mA output of the level sensor when the tank is empty.
Full At
Enter the mA output of the level sensor when the tank is full.
Smoothing Factor
Increase the smoothing factor percentage to dampen the re-sponse to changes. For
example, with a 10% smoothing factor, the next reading shown will consist of an
average of 10% of the previous value and 90% of the current value.
Transmitter
Select the type of transmitter connected (2-wire loop powered, 2-wire
self-powered, 3-wire, or 4-wire.
Name
The name used to identify the transmitter may be changed.
Type
Select the type of sensor to be connected.
5.2.14
DI State
Input Details
The details for this type of input include the current state with a custom message for open versus closed, alarms,
the status of the interlock, and the current type of input setting.
Settings
Touch the Edit icon to view or change the settings related to the sensor.
Open Message
The words used to describe the switch state may be customized.
Closed Message
The words used to describe the switch state may be customized.
Interlock
Choose whether the input should be in the interlocked state when the switch is either
open or closed.
Alarm
Choose if an alarm should be generated when the switch is open, or closed, or if no
alarm should ever be generated.