8
Default temperature
-20
500
Deadband
Low end of sensor range
High end of sensor range
Calibration Required Alarm
0 days
365 days
Sensor Slope (Generic sensor only)
-1,000,000
1,000,000
Sensor Offset (Generic sensor only)
-1,000,000
1,000,000
Low Range (Generic sensor, Virtual Input)
-1,000,000
1,000,000
High Range (Generic sensor, Virtual Input)
-1,000,000
1,000,000
Constant (Virtual Input only)
10% below Low Range setting 10% above High Range setting
Deviation Alarm (Virtual Input)
10% below Low Range setting 10% above High Range setting
4 mA value (Transmitter, AI Monitor analog input only)
0
100
20 mA value (Transmitter, AI Monitor analog input only)
0
100
Max Sensor Range (Fluorometer analog input only)
0 ppb
100,000 ppb
Dye/Product Ratio (Fluorometer analog input only)
0 ppb/ppm
100 ppb/ppm
Set Flow Total (Flowmeter analog input only)
0
1,000,000,000
Flowmeter Max (Flowmeter analog input only)
0
1,000,000
Input Filter (Flowmeter analog input only)
1 mA
21 mA
Totalizer Alarm (Flowmeter analog input only)
0
2,000,000,000
Min Disturbance (Disturbance Virtual Input only)
Low end of sensor range
High end of sensor range
Max Disturbance (Disturbance Virtual Input only)
Low end of sensor range
High end of sensor range
Value at Min Disturbance (Disturbance Virtual Input only)
0
100
Value at Max Disturbance (Disturbance Virtual Input only)
0
100
Stabilization Time (Corrosion only)
0 hours
999 hours
Electrode Alarm (Corrosion only)
0 days
365 days
Alloy Multiplier (Corrosion only)
0.2
5.0
Tank Capacity
0
1,000,000
Empty At
0 mA
21 mA
Full At
0 mA
21 mA
Digital flow meter input settings
Low Limit
High Limit
Totalizer alarm
0
2,000,000,000
Volume/contact for units of Gallons or Liters
1
100,000
Volume/contact for units of m
3
0.001
1,000
K Factor for units of Gallons or Liters
0.01
100,000
K Factor for units of m
3
1
1,000,000
Paddlewheel rate alarm limits
0
High end of sensor range
Paddlewheel rate alarm deadband
0
High end of sensor range
Smoothing Factor
0%
90%
Set Flow Total
0
1,000,000,000
Feed Monitor Input Settings
Low Limit
High Limit
Totalizer Alarm
0 vol. units
1,000,000 vol. units
Set Flow Total
0 vol. units
1,000,000,000 vol. units
Flow Alarm Delay
00:10 Minutes
59:59 Minutes
Flow Alarm Clear
1 Contact
100,000 Contacts
Dead Band
0%
90%
Reprime Time
00:00 Minutes
59:59 Minutes
Volume/Contact
0.001 ml
1,000.000 ml
Smoothing Factor
0%
90%