9
Counter Input Settings
Low Limit
High Limit
DI Counter Rate Alarms
0
30,000
DI Counter Rate Deadband
0
30,000
Totalizer Alarm
0
2,000,000,000
Set Total
0
2,000,000,000
Units per Pulse
0.001
1,000
Smoothing Factor
0%
90%
Remote Modbus Input Settings
Low Limit
High Limit
Alarm Limits
Low end of defined range
High end of defined range
Deadband
Low end of defined range
High end of defined range
Low Range
-1,000,000
1,000,000
High Range
-1,000,000
1,000,000
Reply Timeout
1 second
15 seconds
Remote Register
0
65535
Update Period
00:01 MM:SS
59:59 MM:SS
Timeout Alarm Delay
00:10 MM:SS
59:59 MM:SS
Relay output settings
Low Limit
High Limit
Output Limit Time
1 second
86,400 seconds (0 = unlimited)
Hand Time Limit
1 second
86,400 seconds (0 = unlimited)
Daily Max Time
00:01 MM:SS
23:59 MM:SS (0 = unlimited)
Min Relay Cycle
0 seconds
300 seconds
Set Point
Low end of sensor range
High end of sensor range
Spike Set Point (Spike mode)
Low end of sensor range
High end of sensor range
Onset Time (Spike mode)
0 seconds
23:59:59 HH:MM:SS
Duty Cycle Period (On/Off, Spike, Dual Setpoint modes)
0:00 minutes
59:59 minutes
Duty Cycle (On/Off, Spike, Dual Setpoint modes)
0%
100%
On Delay Time (Manual, On/Off, Dual Setpoint modes, Dual
Switch, Alarm modes, Boolean Logic)
0 seconds
23:59:59 HH:MM:SS
Off Delay Time (Manual, On/Off, Dual Setpoint modes,
Dual Switch, Alarm modes, Boolean Logic)
0 seconds
23:59:59 HH:MM:SS
Dead Band
Low end of sensor range
High end of sensor range
Feed duration (Flow Timer, Counter Timer mode)
0 seconds
86,400 seconds
Accumulator Volume (Flow Timer, Target PPM, PPM
Volume, Volumetric Blend, Flow Meter Ratio modes)
1
1,000,000
Accumulator Setpoint (Counter Timer mode)
1
1,000,000
Feed Percentage (Bleed then Feed mode)
0%
1000%
Feed Lockout Time Limit (Bleed & Feed, Bleed then Feed modes)
0 seconds
86,400 seconds
Prebleed To Conductivity (Biocide mode)
1 (0 = no prebleed)
High end of sensor range
Prebleed Time (Biocide mode)
0 seconds
86,400 seconds
Bleed Lockout (Biocide mode)
0 seconds
86,400 seconds
Event duration (Biocide, Timer modes)
0
30,000
Proportional band (Time/Pulse Proportional mode,
Intermittent Sampling)
Low end of sensor range
High end of sensor range
Sample period (Time Proportional mode)
0 seconds
3600 seconds
Sample Time (Intermittent Sampling mode)
0 seconds
3600 seconds
Hold Time (Probe Wash, Intermittent Sampling modes)
0 seconds
3600 seconds
Maximum Blowdown (Intermittent Sampling mode)
0 seconds
3600 seconds