Faulty wiring of output to pump
Correct wiring
Faulty output board
Repair or replace board
Faulty digital input
Replace board
CONTROLLER, POWER, DISPLAY, OR SENSOR BOARD ERROR
This alarm occurs if the board listed is not recognized
Possible Cause
Correction Action
Poor ribbon cable connection
Remove and reseat ribbon cable, cycle power
Poor option card connection
Remove and reseat the board, cycle power
Faulty board
Return the controller for repair
CONTROLLER, POWER, SENSOR, DISPLAY, NETWORK OR ANALOG OUTPUT BOARD VARIANT
This alarm occurs if the type of board that is detected is not a valid type
Possible Cause
Correction Action
Poor ribbon cable connection
Reseat ribbon cable
Faulty ribbon cable
Replace ribbon cable
Faulty Board
Replace the board listed in the error message
SENSOR SOFTWARE VERSION
This alarm occurs if a sensor input card with software v2.11 or lower is installed onto a controller board running software v2.13 or
higher
Possible Cause
Correction Action
Software is not compatible between boards
Perform a Software Upgrade
INVALID SENSOR TYPE
This alarm occurs if the programmed sensor type is not possible for the installed sensor board
Possible Cause
Correction Action
The sensor board has been removed and replaced with a different type
Reinstall the correct board or reprogram the input to a valid type for
the board installed
INVALID CONTROL MODE
This alarm occurs if the programmed control mode is not possible for the installed power relay board
Possible Cause
Correction Action
The power relay board has been removed and replaced with an
incorrect model
Reinstall the correct board or reprogram the output to a valid type
for the board installed
Fluent LIVE CONNECT ERROR
This alarm occurs if the controller is unable to establish an encrypted connection to the Fluent server. If there is also a Fluent Data
Comm Error, fix that first.
Possible Cause
Correction Action
No UDP support on Port 9012 or TCP support on Port 44965
Open ports/protocols on router
DISABLED (SENSOR, DIGITAL OR VIRTUAL INPUT; RELAY OR ANALOG OUTPUT)
This alarm occurs if software for that input or output did not start correctly
Possible Cause
Correction Action
The software is not functioning
If the error message clears on its own, no action is required.
If the error message persists, cycle power.
If the error message still persists, return the controller for repair.
RELAY OR ANALOG OUTPUT CONTROL FAILURE
This alarm occurs if software for that output did not run correctly
Possible Cause
Correction Action
The software is not functioning
If the error message clears on its own, no action is required.
If the error message persists, cycle power.
If the error message still persists, return the controller for repair.
FRAM FILE SYSTEM ERROR
This alarm occurs if the FRAM is not detected at power up
Possible Cause
Correction Action
The FRAM was or is not functioning
If the error message clears on its own, no action is required.
If the error message persists, cycle power.
If the error message still persists, replace the controller board.