2XX48
Change of value (COV) selection.
Unsigned 16 bits 0...12
0. Temperature
1. Humidity
2. Additional
measurement 1
(CO
2
)
3. Additional
measurement 2
4. Additional
measurement 3
5. Additional
measurement 4
6. External input 1
7. External input 2
8. External input 3
9. External input 4
10.I2C value 1
11.I2C value 2
12.I2C value 3
0
Holding registers for COV settings
Table reading instruction: The register numbers include an XX in the middle. Replace the XX with the
transmitter ID - 1 value. For example, a transmitter with the ID 6: XX = 05.
Note:
The values that are marked with "-" depend on the transmitters' properties.
Regis-
ter
Parameter description
Data type Values
Range
Default
2XX49
COV limit for temperature.
Signed 16
1...500
0,1...50,0 °C
5
2XX50
COV limit for humidity.
Signed 16
1...5000
0,01...50,00 %rH
500
2XX51
COV limit for additional
measurement 1 (CO
2
).
-
-
0
2XX52
COV limit for additional
measurement 2.
-
-
-
0
2XX53
COV limit for additional
measurement 3.
-
-
-
0
2XX54
COV limit for additional
measurement 4.
-
-
-
0
2XX55
COV limit for external
measurement 1.
-
-
-
0
2XX56
COV limit for external
measurement 2.
-
-
-
0
2XX57
COV limit for external
measurement 3.
-
-
-
0
2XX58
COV limit for external
measurement 4.
-
-
-
0
2XX59
COV limit for I2C value 1.
-
-
-
0
2XX60
COV limit for I2C value 2.
-
-
-
0
2XX61
COV limit for I2C value 3.
-
-
-
0
Holding registers for transmitter measurement tuning
Table reading instruction: The register numbers include an XX in the middle. Replace the XX with the
transmitter ID - 1 value. For example, a transmitter with the ID 6: XX = 05.