43 (63)
Regis-
ter
Parameter description
Data type Values
Range
Default
2XX39
External input 2.
Unsigned 16 0 - 1 - 2 - 3 - 4
- 5 - 6
0. Off
1. 0...10 V
2. 0...20 mA
3. Resistance x 0,1
4. Resistance x 10
5. NTC 10
6. Pt1000
0
2XX40
External input 3.
Unsigned 16 0 - 1 - 2 - 3 - 4
- 5 - 6
0. Off
1. 0...10 V
2. 0...20 mA
3. Resistance x 0,1
4. Resistance x 10
5. NTC 10
6. Pt1000
0
2XX41
External input 4.
Unsigned 16 0 - 1 - 2 - 3 - 4
- 5 - 6
0. Off
1. 0...10 V
2. 0...20 mA
3. Resistance x 0,1
4. Resistance x 10
5. NTC 10
6. Pt1000
0
2XX42
I2C input 1.
Unsigned 16 0...65535
Upper 8 bits = I2C
sensor type. Lower 8
bits = value selection
(each known sensor
has list of values that
can be read)
0
2XX43
I2C input 2.
Unsigned 16 0...65535
Upper 8 bits = I2C
sensor type. Lower 8
bits = value selection
(each known sensor
has list of values that
can be read)
0
2XX44
I2C input 3.
Unsigned 16 0...65535
Upper 8 bits = I2C
sensor type. Lower 8
bits = value selection
(each known sensor
has list of values that
can be read)
0
2XX45
Automatic self-calibration of CO
2
measurement.
Unsigned 16 0 - 1
0. Disabled
1. Enabled
1
2XX46
PIR detection delay.
Unsigned 16 0...5
0...5 s
0
2XX47
Measurement update interval.
Unsigned 16 0 / 30...65535
0 = function
disabled,
30...65535 s
0