Published: 18.07.2019
39 (63)
Register
value
Value description
Data type Values
Range
10
Time
Signed 16
0...99
0...99 h
11
Indoor temperature
Signed 16
-1000...1000
-100,0...100,0 °C
C
IN
12
Outdoor temperature
Signed 16
-1000...1000
-100,0...100,0 °C
C
OUT
Holding registers for measurement alarm limits
Regis-
ter
Parameter description
Data type Values
Range
Default
12000
Low temperature alarm limit.
Signed 16
-1000...1000
-100,0...100,0 °C
0
12001
High temperature alarm limit.
Signed 16
-1000...1000
-100,0...100,0 °C
0
12002
Low humidity alarm limit.
Signed 16
0...10000
0...100,00 %rH
0
12003
High humidity alarm limit.
Signed 16
0...10000
0...100,00 %rH
0
12004
Low CO
2
alarm limit.
Signed 16
0...10000
0...10000 ppm
0
12005
High CO
2
alarm limit.
Signed 16
0...10000
0...10000 ppm
0
Holding registers for measurement group settings
Table reading instruction: The register numbers include an X in the middle. Replace the X with the
measurement group number (1...5) you are adjusting.
Note:
The values that are marked with "-" depend on the transmitters' properties.
Regis-
ter
Parameter description
Data type Values
Range
Default
12X00
Measured property.
Unsigned 16 0 - 1 - 2 - 3
0. N/A
1. Temperature
2. Humidity
3. CO
2
0
12X01
Sensor mask.
Unsigned 16 bits 0...11
0. Internal
temperature
1. Internal humidity
2. Internal CO
2
3. Additional
measurement 1
4. Additional
measurement 2
5. Additional
measurement 3
6. Additional
measurement 4
7. Additional
measurement 5
8. External input 1
9. External input 2
10.External input 3
11.External input 4
0
12X02
Transmitters that are included in
the group, ID 1...16.
Unsigned 16 bits 0...15
ID 1...16
0
12X03
Transmitters that are included in
the group, ID 17...32.
Unsigned 16 bits 0...15
ID 17...32
0
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | fax. +358 5 230 9210 | [email protected]
Information is subject to change without prior notice.
EN - 5401comm